background image

Maintenance

8

Outdoor Unit

Maintenance/Repair checklist

1. Water quality control

The plate type heat exchanger is not structured to be disassembled, cleaned or replaced with parts.
To prevent corrosion or scaling on the plate type heat exchanger, special care must be taken to control the water quality. 
Water quality must satisfy the minimum criteria of the reference water quality items. 
When anti-corrosion agent or corrosion inhibitor is added, the substance must not have any corrosive effect on stainless
steel and copper.
Even if the circulating water is not contaminated by the external air, it is recommended to empty the water flowing in the
pipe and to resupply the water. 

2. Flow rate control

If the flow rate is insufficient, it can cause freezing on the plate type heat exchanger. 
Check whether the strainer is clogged or whether the pipe is filled with air and then check the temperature and pressure
difference of the inlet and outlet pipe to check whether the flow rate is insufficient. 
If the temperature and pressure difference is above the appropriate level, it means that the flow rate is reduced. In this
case, the operation must immediately be stopped and re-operated when the root cause is resolved. (*If air is trapped in
the pipe, the air must be purged. Air inside the water pipe interferes with the circulation of the heat water supply and can
cause insufficient flow rate or freezing.)

3. Brine density management

When using the brine (Anti-freeze) in the heat water supply, designated type and density must be used. Calcium chloride
brine can cause corrosion on the plate type heat exchanger and must not be used. 
If the anti-freeze liquid is left as is, it absorbs the moisture from the air to cause a drop in the density, leading to freezing
of plate type heat exchanger. Therefore minimize the contact surface with the atmosphere and periodically measure the
density of the brine to supplement the brine as needed to maintain the density.  

Product operating condition

Heat exchanger cleaning (Wash)

Strainer cleaning

Water quality check

Refrigerant leakage check

Indoor unit filter cleaning

Period (Year)

Checkpoint

• The above checklist is set based on the minimum period and more frequent checking can be required depending on the

operating condition/water quality condition. 

• When cleaning the heat exchanger, make sure to take parts out or lock the value so that chemical detergent does not

penetrate into the pressure gauge etc. 

• When cleaning the heat exchanger, check the connecting part of the water pipes prior to cleaning so that the chemical

detergent does not leak. 

• After sufficiently mixing the chemical detergent with water, start cleaning. 
• Cleaning the heat exchanger is easier at the initial stage and becomes difficult after the scaling has accumulated. 
• In areas where the water quality is poor, cleaning is required periodically.

Because chemical detergent has strong acidity, it must be washed off thoroughly with water. 

• To check whether it is cleaned well inside, remove the hose and check the inside. 
• Purge the air to remove any air inside the water pipe. 
• After checking, always check whether the heat water supply is flowing normally flowing before operating the product. 

1 2 3 4 5 6 7 8 9 10 

11 

12 

13 

14 

15

(

: Check mark)

Daily check/management

Summary of Contents for ARWN Series

Page 1: ... B C RWB DAS4 P NO MFL65003504 Please read this manual carefully before operating your set and retain it for future reference TYPE Outside unit MODELS OWNER S MANUAL AIR CONDITIONER www lg com Copyright 2015 2018 LG Electronics Inc All Rights Reserved ENGLISH ESPAÑOL PORTUGUÊS ...

Page 2: ...sult Ask the dealer or an authorized technician to install the air conditioner Improper installation by the user may result in water leakage electric shock or fire Always ground the product There is risk of fire or electric shock Always intstall a dedicated circuit and breaker Improper wiring or installation may cause fire or electric shock For re installation of the installed product always conta...

Page 3: ...oxygen in the room could result Don t use the existing manifold gage for R22 refrigerant Use the manifold gage for high pressure R410A as possible as for stable refrigerant filling Don t mix and use the R22 pipe and the installation appliances that were used until now Mixing the oil of R22 and R410A may cause failure of the unit due to hydrolysis Operation Do not damage or use an unspecified power...

Page 4: ...unit in a hospital communication station or similar place provide sufficient protection against noise The inverter equipment private power generator high frequency medical equipment or radio communication equipment may cause the air conditioner to operate erroneously or fail to operate On the other hand the air conditioner may affect such equipment by creating noise that disturbs medical treatment...

Page 5: ...ing on the main power switch can result in severe damage to internal parts Keep the power switch turned on during the operational season Do not touch any of the refrigerant piping during and after operation It can cause a burn or frostbite Do not operate the air conditioner with the panels or guards removed Rotating hot or high voltage parts can cause injuries Do not directly turn off the main pow...

Page 6: ...ter paths 3 When running the heater the plate type heat exchanger plays the role of the evaporator and at this time the temperature of the coolant side drops to drop the temperature of the heat water supply which can result in icing point in the water paths 4 And as the heating process progresses the water paths can be partially frozen to lead to damage in plate type heat exchanger 5 As a result o...

Page 7: ...cleaning 3 Connect the water pipe for cleaning with the chemical solvent through the service plug of the pipe and fill up the panel heat exchanger with 50 C 60 C of cleaning solvent and circulate it with the pump for 2 5 hours The circulation time may depend on the temperature of the cleaning solvent or the creation of the scales Therefore observe change in the color of the chemical solvent to set...

Page 8: ...Calcium chloride brine can cause corrosion on the plate type heat exchanger and must not be used If the anti freeze liquid is left as is it absorbs the moisture from the air to cause a drop in the density leading to freezing of plate type heat exchanger Therefore minimize the contact surface with the atmosphere and periodically measure the density of the brine to supplement the brine as needed to ...

Page 9: ...f required Be careful not to let air in If so the water velocity will be unstable in the circulation pump efficiency will also decrease and may cause the piping vibration Therefore install the air purge where it may generate the air Choose the following anti freezing methods Otherwise it will be dangerous for the pipe to break in the winter Circulate the water with the pump before dropping the tem...

Page 10: ...i corrosion agent or removing the air can be very effective 3 In case of using the closed type cooling tower the cooling water and supplementing water must satisfy the water quali ty criteria of closed type system in the table 4 Supplementing water and supplied water must be supplied with tap water industrial water and underground water excluding filtered water neutral water soft water etc 5 15 it...

Page 11: ...Sor Juana lnés de la Cruz No 555 Col San Lorenzo Industrial Tlalnepantla de Baz Estado de México C P 54033 Tel 55 5321 1919 Teléfono sin costo 01 800 347 1919 Página web http www lg com mx ...

Reviews: