9
ENGLISH
CAUTION
• In case of on the floor you should not have to fix the compressor
module with anchor bolts.
• In case of on the structure you can fix the Compressor module
securely use anchor bolts, nuts and washers to the structure.
The foundation must be larger than the image
• If noise / vibration occurs, install rubber pad under the product
• Be sure to remove the Pallet(Wood Support) of the bottom side
of the compressor module before welding.
Not removing Pallet(Wood Support) causes hazard of fire during
welding.
• When vibration is transmitted to the building, use a vibration
proof rubber (field supply).
Pallet(Wood Support)
- Remove before Installation
!
INSTALLATION : HEAT
EXCHANGER MODULE
- Install the unit above the ceiling correctly.
CASE 1
Position of suspension Bolt
- Apply a joint-canvas between the module and duct to absorb
unnecessary vibration.
CASE 2
- Install the module leaning to a drainage hole side as a figure for easy
water drainage.
Position of console Bolt
- A place where the module will be leveled and that can support the
weight of the unit.
- A place where the module can withstand its vibration.
- A place where service can be easily performed.
Dimension
Chassis
A
B
C
D
E
F
G
H
I
J
K
L
B8
1680 1565 1160 330 460 580 700 1400 1635 390 445 15
(Unit:mm)
B8 Chassis
M10 Nut
M10 washer
X 4
X 4
M10 Nut
M10 washer
X 4
X 8
NOTE
!
• Throughly study the following installation locations:
1. In such places as restaurants and kitchens, considerable
amount of oil steam and flour adhere to the fan, the fin of
the heat exchanger, resulting in heat exchange reduction,
spraying, dispersing of water drops, etc.
In these cases, take the following actions:
• Make sure that the ventilation fan for smoke-collecting hood on a
cooking table has sufficient capacity so that it draws oily steam
which should not flow into the suction of the air conditioner.
• Make enough distance from a cooking room to install the air
conditioner in such a place where it may not suck in oil steam.
2. Avoid installing air conditioner in such circumstances where cutting
oil mist or iron powder is in suspension in factories, etc.
3. Avoid places where inflammable gas is generated, flows in, is stored
or vented.
4. Avoid places where sulfurous acid gas or corrosive gas is generated.
5. Avoid places near high frequency generators.