OUTDOOR UNITS INFORMATION
9
ENGLISH
CAUTION
!
• Ratio of the connectable Indoor Units to the Outdoor: Within 50 ~ 160 %
• Ratio of running Indoor Units to the Outdoor: Within 10 ~ 100 %
• A combination operation over 100 % cause to reduce each indoor unit capacity.
OUTDOOR UNITS INFORMATION
Series / Phase
0 Series / 3Ø
System(HP)
8
10
12
Refrigerant Precharged
Amount
kg
3.5
4.5
6
lbs
7.7
9.9
13.2
Net weight
kg
115
144
157
lbs
254
317
346
Dimensions (WxHxD)
mm
950 x 1 380 x 330
1 090 x 1 625 x 380 1 090 x 1 625 x 380
inch
37.4 x 54.3 x 13.0
42.9 x 64.0 x 15.0
42.9 x 64.0 x 15.0
Piping
Connections
Liquid Pipes
mm(inch)
Ø 9.52(3/8)
Ø 9.52(3/8)
Ø 12.7(1/2)
Gas Pipes
mm(inch)
Ø 19.05(3/4)
Ø 22.2(7/8)
Ø 28.58(11/8)
Series / Phase
5 Series / 3Ø
System(HP)
4
5
6
Refrigerant Precharged
Amount
kg
1.8
2.4
2.4
lbs
4.0
5.3
5.3
Net weight
kg
65
72
72
lbs
143
159
159
Dimensions (WxHxD)
mm
950 x 834 x 330
950 x 834 x 330
950 x 834 x 330
inch
37.4 x 32.8 x 13.0
37.4 x 32.8 x 13.0
37.4 x 32.8 x 13.0
Piping
Connections
Liquid Pipes
mm(inch)
Ø 9.52(3/8)
Ø 9.52(3/8)
Ø 9.52(3/8)
Gas Pipes
mm(inch)
Ø 15.88(5/8)
Ø 15.88(5/8)
Ø 19.05(3/4)
Series / Phase
0 Series / 3Ø
System(HP)
Refrigerant Precharged
Amount
kg
lbs
Net weight
kg
lbs
Dimensions (WxHxD)
mm
inch
Piping
Connections
Liquid Pipes
mm(inch)
Gas Pipes
mm(inch)
4
5
6
3
3
3
6.6
6.6
6.6
96
96
96
212
212
212
950 x 1 380 x 330
950 x 1 380 x 330
950 x 1 380 x 330
37.4 x 54.3 x 13.0
37.4 x 54.3 x 13.0
37.4 x 54.3 x 13.0
Ø 9.52(3/8)
Ø 9.52(3/8)
Ø 9.52(3/8)
Ø 15.88(5/8)
Ø 15.88(5/8)
Ø 19.05(3/4)