18
ENGLISH
Pipe Connection Method/Precautions for
Series connections between Outdoor units
- Separate Y branch joints are needed for series connections between
outdoor units.
- Please refer to the below connection examples to install pipe connec-
tions between outdoor units.
- If the distance between the outdoor units becomes more than 2m,
apply Oil Traps between the gas pipes.
- If the outdoor unit is located lower than the main pipe, apply Oil Trap.
Pipe connection between outdoor
units (General Case)
The maximum pipe
length after the first
branching between the
outdoor units is 10m or
less
Pipes between outdoor units
are 2m or less
Examples of Wrong Pipe Connections
2m or less
Pipes between outdoor units
are 2m or longer
Oil Trap
Oil Trap
Oil Trap
2m or less
2m or less
2m or less
0.2m or more
2m or longer
2m or longer
2m or longer
If the main pipe is
higher than the
outdoor units, oil is
accumulated in the
outdoor unit.
If there are differences in the height
between the outdoor units, oil is
accumulated in the lower outdoor unit.
Oil Trap
Toward indoor unit
Toward indoor unit
Pipe inclination (2° or more)
Toward indoor unit
Toward indoor unit
Toward indoor unit
Toward indoor unit
(Example 1)
(Example 2)
(Example 3)
- Apply Oil Trap as shown below when the length of the pipe between
the outdoor units is more than 2m. Otherwise, the unit may not oper-
ate properly.
(Example 1)
Toward indoor unit
Toward indoor unit
2m
2m
2m
0.2m
Oil Trap
(Example 2)
- When connecting the pipes between the outdoor units, the accumu-
lation of oil in the slave outdoor unit should be avoided. Otherwise,
the unit may not operate properly.
(Example 1)
Toward indoor unit
Toward indoor unit
h
Toward indoor unit
(Example 2)
Summary of Contents for ARUB120LTE4
Page 40: ...40 ENGLISH ...
Page 41: ......