Outdoor unit Connection
Indoor Unit Connection
Indoor Unit connecting pipe from branch (a,b,c,d,e,f)
Indoor Unit capacity
[kW(Btu/h)]
Liquid pipe
[mm(inch)]
Gas pipe [mm(inch)]
≤
5.6(19,100)
Ø6.35(1/4)
Ø12.7(1/2)
< 16.0(54,600)
Ø9.52(3/8)
Ø15.88(5/8)
< 22.4(76,400)
Ø9.52(3/8)
Ø19.05(3/4)
< 28.0(95,900)
Ø9.52(3/8)
Ø22.2(7/8)
WARNING
• In case of pipe diameter B connected after first branch is bigger
than the main pipe diameter A, B should be of the same size
with A.
Ex) In case indoor unit combination ratio 120% is connected to
70kW outdoor unit.
1) Outdoor unit main pipe diameter A : Ø34.9(Low pressure
gas pipe), Ø15.88(liquid pipe), Ø28.58(High Pressure liq-
uid pipe)
2) Pipe diameter B after first branch according to 120% in-
door unit combination(84kW) : Ø34.9(Low pressure gas
pipe), Ø19.05(liquid pipe), Ø28.58(High Pressure liquid
pipe)
Therefore, pipe diameter B connected after first branch
would be Ø34.9(Low pressure gas pipe), Ø15.88(liquid
pipe), Ø28.58(High Pressure liquid pipe) which is same
with main pipe diameter.
[Example]
Do not choose the main pipe diameter by downward indoor unit
total capacity but its outdoor unit model name.
Do not let the connection pipe from branch to branch exceed the
main pipe diameter chosen by outdoor unit model name.
EX) Where connecting the indoor units to the 22 HP (61.5 kW)
outdoor unit to 120% of its system capacity (73.8 kW) and
branching 7k (2.1kW) indoor unit at the 1st branch
Main pipe diameter(22 HP outdoor unit): Ø28.58(Low pressure
gas pipe), Ø15.88(Liquid pipe), Ø22.2(High pressure gas pipe)
Pipe diameter between 1st and 2nd branch (71.7kW indoor units):
Ø34.9(Gas pipe) Ø19.05(Liquid pipe) in conformity with down-
ward indoor units.
Since the main pipe diameter of 22HP outdoor unit is
Ø28.58(Low pressure gas pipe), Ø15.88(Liquid pipe), Ø22.2(High
pressure gas pipe) is used as the main pipe and the connection
pipe between 1st and 2nd branch.
!
CAUTION
• Bending radius should be
at least twice the diameter
of the pipe.
• Bend pipe after 500mm or
more from branch(or
header).
Do not bend U type.
It may cause Performance
unsatisfactory or noise.
!
500mm or more
500mm or more
Pattern 7
Pattern 8
HR1
A
A
A
48k
48k
1
2
• * : Serial connection of HR units : Capacity sum of indoor units ≤ 192 kBtu/h
• * : Maximum indoor units per a branch are 8 indoor units
HR2
48k
48k
3
4
HR3
48k
48k
5
6
*
HR1
48k
48k
1
2
HR2
*
B
12k
12k
12k
12k
3
4
5
6
24k
7
24k
8
• Pipe installation from outdoor units to HR units
: 3 pipes(Low pressure Gas pipe, High pressure Gas pipe, Liquid pipe)
• Pipe installation from HR units to indoor units
: 2 pipes(Gas pipe, Liquid pipe)
B
A
1
HR1
Outdoor
Unit
Indoor Unit
Y Branch pipe
Low pressure Gas pipe
High pressure Gas pipe
Liquid pipe
Gas pipe
Liquid pipe
Head Branch pipe
Indoor
Unit
Keep the 40m distance from the first branch to the farthest indoor.
5m(16ft)
15m(49ft)
1) under 40m
Keep the sum of indoor capacity under 56.4kW(192 kBtu/h).
Indoor
Unit
Indoor
Unit
Indoor
Unit
Indoor
Unit
Indoor
Unit
Indoor
Unit
Indoor
Unit
Indoor
Unit
Indoor
Unit
Indoor
Unit
Indoor
Unit
Indoor
Unit
1) under 40m
Y branch
Keep the sum of indoor capacity under 56.4kW(192 kBtu/h).