Installation Manual
15
Installation
ENGLISH
HAND OVER
Teach the customer the operation and maintenance procedures, using the operation manual.
(air filter cleaning, temperature control, etc.)
The Power cord connected to the unit should be selected according to the following
specifications.
CAUTION
!
Make sure that the screws of the terminal are free from looseness.
WARNING
!
After the confirmation of the above conditions, prepare the wiring as follows:
1) Never fail to have separate power specially for the air conditioner. As for the method of wiring, follow
the circuit diagram pasted on the inside of control box cover.
2) Provide a circuit breaker switch between power source and the unit.
3) The screw which fasten the wiring in the casing of electrical fittings are liable to come loose from
vibrations to which the unit is subjected during the course of transportation. Check them and make
sure that they are all tightly fastened. (If they are loose, it could give rise to burn-out of the wires.)
4) Confirm the Specification of power source
5) Confirm that electrical capacity is sufficient.
6) Be sure that the starting voltage is maintained at more than 90 % of the rated voltage marked on the
name plate.
7) Confirm that the cable thickness is as specified in the power sources specification.
(Particularly note the relation between cable length and thickness.)
8) Do not install the leakage breaker in a place which is wet or moist.
Water or moist may cause short circuit.
9) The following troubles would be caused by voltage drop-down.
• Vibration of a magnetic switch, damage on the contact point there of, fuse breaking, disturbance to the
normal function of a overload protection device.
• Proper starting power is not given to the compressor.
CAUTION
!
※
Resistance measurement position for incorrect wiring. (TY / 4 / 2 / 1 Way)
• Communication and Power Cable (TY / 4 / 2 / 1 Way)
1. Communication Cable : CVV-SB 1.0~1.5x2C
2. Power Cable : H07RN-F 1.5x3C
Terminal Block Indoor
1(L)
2(N)
3
4
INDOOR
POWER INPUT
A
-
-
-
-
B
A
B
A
B
GND 12 V
DRY2
DRY1
INTERNET
Terminal Block of outdoor unit
IDU
SODU
Outdoor
Unit
• TU/TT Chassis
1 Way
Summary of Contents for ARNU36GTYB4