Installation Manual
17
Installation
ENGLISH
LGAP Network System
Master
Slave
GND
Signal
12 V
or
Display Error Message
Master
Slave
Slave
Slave
4. 2 Remote Control
n
Wired remote controller 2 + Indoor unit 1
1. It is possible to connect two wired remote controllers (Max.) with one indoor unit.
Set only one indoor unit to Master, set the others to Slave.
Set only one wired remote controller to Master, set the others to Slave.
2. Every types of indoor unit is possible to connect two remote controller.
3. It is possible to use wireless remote controller at the same time.
4. It is possible to connect with Dry Contact and Central controller at the same time.
5. In case that any error occurs at indoor unit, the error code is displayed on the wired
remote controller.
6. There isnʼt limits of indoor unit function.
5. Accessories for group control setting
It is possible to set group control by using below accessories.
Indoor unit 2 EA +Wired remote controller
Indoor unit 1 EA +Wired remote controller 2EA
h
PZCWRCG3 cable used for connection
h
PZCWRC2 cable used for connection
S lave
Mas te r
Maste r
PZC WRC G3
Maste r
S lave
PZC WRC 2
• Apply totally enclosed noncombustible conduit in case of local building code Requiring plenum cable usage.
CAUTION