Troubleshooting Guide
- 272 -
Copyright ©2009 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
1. Loose connection of temperature sensor con-
nector
2. Defect of temperature sensor (Open/Short)
3. Defect of Fan Main PCB
Error
No.
Error Type
Error Point
Main Reasons
Abnormal value of sensor
(Open/Short)
Heat sink temperature sensor
error of inverter control PCB
65
■
Error diagnosis and countermeasure flow chart
* If value is 100K
Ω ↑
(open) or 100
Ω ↓
(short), error occurs
NB: Resistance value of temperature sensor change according to temperature
It is normal if value shown as below (±5% error)
Heat sink sensor(±5% tolerance) : 10°C = 20.0K
Ω
: 25°C= 10.0K
Ω
: 50°C= 3.5K
Ω
: 85°C= 1.0K
Ω
Temperature sensor location of Heat sink
Is sensor connected
to PCB correctly?
Is value of sensor
resistance normal?*
Connect PCB to sensor
Replace sensor
Replace inverter fan PCB
Yes
Yes
No
No
Measure the resistance of heat sink temperature sensor