Troubleshooting Guide
- 251 -
Copyright ©2009 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
06
Refer to CH02
Error
No.
Error Type
Error Point
Main Reasons
Indoor unit outlet pipe
temperature sensor open
or short
Indoor unit outlet pipe
temperature sensor
error
07
1. Indoor units are in different mode
2. PCB fault
3. cabled remote controller fault
Error
No.
Error Type
Error Point
Main Reasons
The Indoor units started
later are operated in dif-
ferent mode from earlier
one.
All Indoor units are not
running in same mode
09
1. Error developed in transmission between the
micro- processor and the EEPROM on the sur-
face of the PCB.
2. ERROR due to the EEPROM damage
Error
No.
Error Type
Error Point
Main Reasons
Problem in EEPROM
inside Indoor PCB ASS’Y
EEPROM
Indoor unit EEPROM
error
■
Error diagnosis and countermeasure flow chart
■
Error diagnosis and countermeasure flow chart
* Outdoor main PCB dip switch no.5 (Cooling) or no.6 (heating) is in On, different mode operation error
may be occurred because the operation mode is fixed by dip switch setting.
** Dissolution method CH07 with remote controller
1) Error removal method : Turn off remote controller by pressing the On/Off button on the cabled remote controller.
The error code will be removed automatically after a few seconds.
With cableless remote controller: Turn off indoor unit, and turn on with the other operation mode
the error will disappeared
2) Immediately change the operation mode after the pressing the On/Off button .
The same operation mode as in the indoor unit started at first other than the defective unit mode (heating /cooling)
*** After replacing the indoor unit PCB, it should be done to do Auto addressing and input the address of central control
- Replace the indoor unit PCB, and then make sure to do Auto addressing and input the address of central control
Is operation mode of
outdoor & Indoor units
same?
Adjust outdoor main PCB
dip switch setting *
Yes
No
END
Is error code
disappeared
after set operation
mode same?**
Replace Indoor PCB***
No
Yes