Troubleshooting Guide
- 256 -
Copyright ©2009 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
23
DC voltage charging for
inverter compressor driving
defect
Error
No.
Error Type
Error Point
Main Reasons
Problem in DC charging volt-
age after starting relay
turned on
1. Looseness of DC link terminal
2. Damage in starting relay
3. Capacitor damage
4. Defective sensing circuit of the inverter PCB
■
Error diagnosis and countermeasure flow chart
Replace Capacitor
Is noise filter and
fuse normal?
[refer electric
component part]
No
Replace Noise Filter or Fuse
Is capacitor normal?
[refer electric
component part]
Yes
No
Yes
Is the voltage of 3 phase
diode more than maximum
270V?*
No
Check whether all the
connections and terminals
is normal and reconnect
Yes
* After indoor unit turned on and the compressor is not operated,
just before magnetic switch is turned on
the voltage between the 2 terminal as below is more than 270V
Replace outdoor unit inverter PCB