INSTALLATION OF OUTDOOR UNIT
7
ENGLISH
- If an awning is built over the unit to prevent direct sunlight or rain exposure, make sure that
heat radiation from the condenser is not restricted.
- Ensure that the spaces indicated by arrows around front, back and side of the unit.
- Do not place animals and plants in the path of the warm air.
- Take the air conditioner weight into account and select a place where noise and vibration are
minimum.
- Select a place so that the warm air and noise from the air conditioner do not disturb neighbors.
More than
300 mm
Fence or
obstacles
More than 700 mm
More than 600 mm
More than
300mm
More than
300 mm
Sunr
oof
Unit : mm
Installation Places
INSTALLATION OF OUTDOOR UNIT
Piping length and the elevation
Ceiling Suspended Air conditioner
MODEL
Pipe Size
Length A (m)
Elevation B (m)
Additional
Refrigerant (g/m)
Gas
Liquid
Standard Max. Standard Max.
Ø 15.88(5/8) Ø 9.52(3/8)
Ø 12.7 (1/2) Ø 6.35 (1/4)
40
7.5
50
5
30
7.5
30
15
20
5
APUQ18GS1K1
Ø 15.88(5/8) Ø 9.52(3/8)
40
7.5
50
5
30
ATUQ24GQSK1
ATUQ18GQSK1
Ø 12.7 (1/2) Ø 6.35 (1/4)
7.5
30
15
20
5
APUQ30GS1K1