background image

1

Mount the tubing holder in the original
position.

2

Ensure that the hooks are properly seated
on the installation plate by moving it left
and right.

3

Press the lower left and right sides of the
unit against the installation plate until the
hooks engage into their slots (clicking
sound).

4

Finish the assembly by screwing the unit
to the installation plate by using two pieces
of type "C" screws. And assemble a chas-
sis cover.

* The feature can be changed according to

type of model.

Finishing the indoor unit 
installation

Type 'C' screw

Checking the Drainage

1

Pour a glass of water on the evaporator.

2

Ensure the water flows through the drain
hose of the indoor unit without any leak-
age and goes out the drain exit.

* The feature can be changed according to

type of model.

1

The drain hose should point downward for
easy drain flow.

Drain piping

Downward slope

Drain pan

Drain

hose

Leakage

checking

Connecting area

drain hose

Leakage

checking

To check the drainage.

CAUTION

!

The indoor unit can be dropped from the
wall, the indoor unit is not screwed
correct position on the install plate.

To avoid the gap between the indoor unit
and wall , screw the indoor unit to the
install plate correctly.

To avoid nitrogen entering the refrigerant
system in a liquid state, the top of the cylin-
der must be higher than its bottom when
you pressurize the system. Usually, the cylin-
der is used in a vertical standing position.

Air Purging

The air and moisture remaining in the
refrigerant system have undesirable effects as
indicated below.

1

Pressure in the system rises.

2

Operating current rises.

3  

Cooling(or heating) efficiency drops.

4  

Moisture in the refrigerant circuit may
freeze and block capillary tubing.

5  

Water may lead to corrosion of parts in the
refrigeration system.

Therefore, after evacuating the system, take a
leak test for the piping and tubing between
the indoor and outdoor unit.

Air purging with vacuum pump

1

Preparation
- Check that each tube(both liquid and gas

side tubes) between the indoor and out-
door units have been properly connected
and all wiring for the test run has been
completed. Remove the service valve
caps from both the gas and the liquid side
on the outdoor unit. Note that both the
liquid and the gas side service valves on
the outdoor unit are  kept closed at this
stage.

2  

Leak test
- Connect the manifold valve(with pressure

gauges) and dry nitrogen gas cylinder to
this service port with charge hoses.

Seal a small opening 
around the pipings 
with gum type sealant.

Trap

Trap

- Do a leak test of all joints of the tubing(both

indoor and outdoor) and both gas and liquid
side service valves. Bubbles indicate a leak.
Be sure to wipe off the soap with a clean
cloth.

- After the system is found to be free of leaks,

relieve the nitrogen pressure by loosening
the charge hose connector at the nitrogen
cylinder. When the system pressure is
reduced to normal, disconnect the hose from
the cylinder.

There is a risk of fire and explosion.
Inert gas (nitrogen) should be used

when you check plumbing leaks, cleaning
or repairs of pipes etc. If you are using
combustible gases including oxygen,
product may have the risk of fires and
explosions.

Be sure to use a manifold valve for air purg-
ing. If it is not available, use a stop valve for
this purpose. The knob of the 3-way valve
must always be kept close.

- Pressurize the system to maximum 

17.6 kg/cm

2

G (R22 model) or 28.1 kg/cm

2

G

(R410A model) with dry nitrogen gas and
close the cylinder valve when the gauge
reading reaches 17.6 kg/cm

2

G (R22 model)

or 28.1 kg/cm

2

G (R410A model). Next step

is leak test with liquid soap.

Indoor unit

Outdoor unit

Manifold valve

Charge hose

Nitrogen gas
cylinder(in vertical
standing position)

Pressure 
gauge

NOTE

CAUTION

!

WARNING

!

2

Do not make drain piping like the 
following.

* The feature can be changed according to

type of model.

Installing drain piping of the
outdoor unit

Depending on installation site, it may be
required to install drain plug for drainage
(Supplied with the unit). In cold areas, do not
use a drain hose with the outdoor unit.
Otherwise, drain water may freeze, impairing
the heating performance.

1

See the figure below for installation of the
drain plug.

A   Drain nipple
B   Drain cap
C   Drain washer

2

Connect a field supplied vinyl hose to the
drain nipple (A). If the hose is too long and
hangs down, fix it carefully to prevent kinks. 

* The feature can be changed according to

type of model.

Do not raise

Water
leakage

Tip of drain hose 
dipped in water

Water
leakage

Ditch

Less than 
50mm gap

Accumulated
drain water

Air

Waving

Water
leakage

B

A

C

• 6.6 kW

• 2.5/3.5/5.0 kW

Forming the Piping

Form the piping by wrapping the connecting
portion of the indoor unit with insulation material
and secure it with two kinds of vinyl tapes.

- If you want to connect an additional drain

hose, the end of the drain outlet should be
routed above the ground. Secure the drain
hose appropriately.

In cases where the outdoor unit is installed
below the indoor unit perform the following.

1   

Tape the piping, drain hose and connecting
cable from down to up.

2

Secure the tapped piping along the exteri-
or wall using saddle or equivalent.

* The feature can be changed according to

type of model.

In cases where the Outdoor unit is installed
above the Indoor unit perform the following.

1   

Tape the piping and connecting cable from
down to up.

2

Secure the taped piping along the exterior
wall. Form a trap to prevent water entering
the room.

3

Fix the piping onto the wall using saddle or
equivalent.

Drain hose

Vinyl tape(narrow)

Pipe

Wrap with
vinyl tape(wide)

Taping

Saddle

Drain hose

Pipings

Connecting cable

Seal a small opening 
around the pipings 
with gum type sealant.

Trap is required to prevent water
from entering into electrical parts.

- Remove the caps from the 2-way and 3-way

valves.

- Remove the service-port cap from the 3-way

valve.

- Apply a soap water or a liquid neutral deter-

gent on the indoor unit connection or out-
door unit connections by a soft brush to
check for leakage of the connecting points of
the piping.

- If bubbles come out, the pipes have leakage

- Connect the charge hose end described in

the preceding steps to the vacuum pump to
evacuate the tubing and indoor unit. Confirm
the "Lo" knob of the pressure Gauge is open.
Then, run the vacuum pump. The operation
time for evacuation varies with tubing length
and capacity of the pump. The following table
shows the time required for evacuation.

Soap water method

Evacuation

* The feature can be changed according

a type of model.

- When the desired vacuum is reached, close

the knob of the 3-way valve and stop the
vacuum pump.

- With a service valve wrench, turn the valve

of liquid side counter-clockwise to fully open
the valve

- Turn the valve of gas side counter-clockwise

to fully open the valve

- Loosen the charge hose connected to the

gas side service port slightly to release the
pressure, then remove the hose.

- Replace the flare nut and its bonnet on the

gas side service port and fasten the flare nut
securely with an adjustable wrench. This
process is very important to prevent leakage
from the system

- Replace the valve caps at both gas and liquid

side service valves and fasten them tight.
This completes air purging with a vacuum
pump.

- Replace the pipe cover to the outdoor unit by

one screw. Now the air conditioner is ready
for test run.

Finishing the Job

Gas side

Outdoor unit

Liquid side

Cap

3-way or

2-way valve

3-way valve

Required time for evacuation when 30 gal/h

vacuum pump is used

If tubing length is

less than 10 m 

(33 ft)

If tubing length is

longer than 10 m

(33 ft)

10 min. or more

15 min. or more

for R32 Only

• Electronic leak detectors shall be used to

detect flammable refrigerants, but the sensi-
tivity may not be adequate, or may need re-
calibration. (Detection equipment shall be cal-
ibrated in a refrigerant-free area.)

• Leak detection equipment shall be set at a

percentage of the LFL (Lower flammable
limit) of the refrigerant and shall be calibrated
to the refrigerant employed and the appropri-
ate percentage of gas (25 % maximum) is
confirmed.

• Leak detection fluids are suitable for use with

most refrigerants but the use of detergents
containing chlorine shall be avoided as the
chlorine may react with the refrigerant and
corrode the copper pipe-work.

• If a leak is suspected, all naked flames shall

be removed/extinguished.

• If a leakage of refrigerant is found which

requires brazing, all of the refrigerant shall be
recovered from the system, or isolated (by
means of shut off valves) in a part of the sys-
tem remote from the leak.

• Oxygen free nitrogen (OFN) shall be purged

through the system both before and during
the brazing process.

NOTE

* How to enter the installer mode

* How to set the code

11

12

Summary of Contents for AM07BP.NSJ

Page 1: ...he appliance shall be installed in accordance with national wiring regulations Compliance with national gas regulations shall be observed Means for disconnection must be incorporated in the fixed wiring in accordance with the wiring rules If the supply cord is damaged it must be replaced by the man ufacturer or its service agents or similarly qualified person in order to avoid a hazard Appliance s...

Page 2: ...or con sumer purposes not a precision refrigerant system There is risk of damage or loss of property Do not install the unit in potentially explosive atmospheres Refrigerant for R32 Only WARNING The appliance shall be stored in a well ventilated area where the room size corresponds to the room area as specified for operation The appliance shall be stored in a room without continuously operating op...

Page 3: ... Spanner Torque wrench Multi meter Hexagonal wrench Ammeter Gas leak detector Thermometer Level Flaring tool set Name Select the best Location There should not be any heat or steam near the unit Select a place where there are no obstacles around of the unit Make sure that condensation drainage can be conveniently routed away Do not install near a doorway Ensure that the interval between a wall and...

Page 4: ...rrs removal 1 Completely remove all burrs from the cut cross section of pipe tube 2 While removing burrs put the end of the copper tube pipe in a downward direction while removing burrs location is also changed in order to avoid dropping burrs into the tubing Putting nut on Remove flare nuts attached to indoor and outdoor unit then put them on pipe tube having completed burr removal not possible t...

Page 5: ...es according to color codes referring to the wiring diagram NOTE The power cord connected to unit should be selected according to the following national wiring regulations The supply cords of parts of appliances for outdoor use shall not be lighter than polychloroprene sheathed flexible cord code designation 60245 IEC 57 H05RN F CAUTION Outdoor unit 1 Remove the tubing cover from the unit by loose...

Page 6: ...r 2 Connect a field supplied vinyl hose to the drain nipple A If the hose is too long and hangs down fix it carefully to prevent kinks The feature can be changed according to type of model Do not raise Water leakage Tip of drain hose dipped in water Water leakage Ditch Less than 50mm gap Accumulated drain water Air Waving Water leakage B A C 6 6 kW 2 5 3 5 5 0 kW Forming the Piping Form the piping...

Page 7: ...3 Reattach the cover by pushing it back into position If you press and hold the On Off button for 3 5 seconds instead of 6 seconds the unit will switch to the test operation In the test operation the unit blows out strong air for cooling for 18 minutes and then returns to the factory default settings This is performed when the unit is relocated or the refrigerant circuit is serviced Pump Down mean...

Page 8: ...lti model refer to Multi outdoor unit installation manual Capacity kW Pipe Size Standard Length m Max Length Ⓐ m Max Elevation Ⓑ m Additional Re frigerant g m GAS LIQUID mm inch mm inch 2 5 3 5 Ø9 52 3 8 Ø6 35 1 4 7 5 20 10 20 5 0 Ø12 7 1 2 Ø6 35 1 4 7 5 20 10 20 6 6 Ø15 88 5 8 Ø6 35 1 4 7 5 30 15 30 Capacity Mode Indoor temperature Outdoor temperature 2 5 3 5 kW Cooling 18 C 32 C 15 C 48 C Heatin...

Reviews: