background image

Fixing Installation Plate

The wall you select should be strong and solid
enough to prevent vibration

1

Mount the installation plate on the wall with type
"A" screws. If mounting the unit on a concrete
wall, use anchor bolts.

- Mount the installation plate horizontally by

aligning the centerline using Horizontal  meter.

2

Measure the wall and mark the centerline.
It is also important to use caution concern-
ing the location of the installation plate.
Routing of the wiring to power outlets is
through the walls typically. Drilling the hole
through the wall for piping connections
must be done safely.

Drill a Hole in the Wall

- Drill the piping hole with a ø65mm hole core

drill. Drill the piping hole at either the right or
the left with the hole slightly slanted to the
outdoor side.

Flaring Work

Main cause for gas leakage is due to defect of
flaring work. Carry out correct flaring work in
the following procedure.

Cut the pipes and the cable

1

Use the piping kit accessory or the pipes
purchased locally.

2

Measure the distance between the indoor
and the outdoor unit.

3

Cut the pipes a little longer than measured
distance.

4

Cut the cable 1.5 m longer than the pipe
length.

5-7 mm

(3/16"~5/16")

Indoor

WALL

Outdoor

Copper

pipe

90°

Slanted   Uneven  Rough

• Use the deoxidised copper as piping

materials to install. 

NOTE

C Type:  494

C Type:  504

Place a level on raised tab

Place a level on raised tab

Unit Outline

Unit Outline

83

C Type:  134

Measuring Tape

Ø65

83

Ø65

134

178

Measuring Tape

Hanger

Ø65

76

113

Ø65

C Type:  150

194

152

Ø65

Right r

ear piping

Right r

e

ar piping

Right r

e

ar piping

L

e

ft r

ear piping

L

e

ft r

ear piping

L

e

ft r

ear piping

(Unit : mm)

Ø65

C Type : 134

C Type : 98

C Type

C Type : 418

C Type : 418

Place a level on raised tab

Unit Outline

Installation Plate

407

397

3

Pull back the tubing holder.

4

Remove pipe port  cover and positioning
the tubing

* The feature can be changed according to

type of model.

1

Insert 4 hooks of the chassis cover into
gap of the chassis certainly.

2

Push the 6 point hook to assemble chassis
cover. Push the chassis cover 

① → ②

.

Assembly of chassis cover

Right

Indoor unit back side view

Tubing holder

Left

Backwards

-  Press on the tubing cover and unfold the

tubing to downward slowly. And then bend
to the left side slowly.

* The feature can be changed according to

type of model.

- Following bending case from right to left

directly may cause damage to the tubing.

* The feature can be changed according to

type of model.

Good case

Bad case

To protect the chassis cover bended,
assembly chassis cover correctly.

Installation Information. For right piping.
Follow the instruction above.

NOTE

NOTE

Burrs removal

1   

Completely remove all burrs from the cut
cross section of pipe/tube.

2   

While removing burrs put the end of the
copper tube/pipe in a downward direction
while removing burrs location is also
changed in order to avoid dropping burrs
into the tubing.

Putting nut on

- Remove flare nuts attached to indoor and

outdoor unit, then put them on pipe/tube
having completed burr removal.
(not possible to put them on after finishing
flare work)

Flaring work

1

Firmly hold copper pipe in a bar with the
dimension shown in below table.

2

Carry out flaring work with the flaring tool.

Check

1

Compare the flared work with the figure
by.

2

If a flared section is defective, cut it off
and do flaring work again.

Connecting the Piping

1

Pull the cover at the bottom of the indoor
unit. Pull the cover 

① → ②

.  

2

Remove the cover from the indoor unit.

Pipe

Reamer

Point down

Flare nut

Copper tube

• Temper grade of pipe: Annealed.

• When flared joints are reused indoors,

the flare part shall be re-fabricated.

NOTE

NOTE

Pipe diameter

Inch (mm)

A inch (mm)

Wing nut type 

Clutch type 

Ø 1/4 (Ø 6.35)

0.04~0.05(1.1~1.3)

0~0.02

(0~0.5)

Ø 3/8 (Ø 9.52)

0.06~0.07(1.5~1.7)

Ø 1/2 (Ø 12.7)

0.06~0.07(1.6~1.8)

Ø 5/8 (Ø 15.88) 0.06~0.07(1.6~1.8)

Ø 3/4 (Ø 19.05) 0.07~0.08(1.9~2.1)

Bar

Copper pipe

"A"

<Wing nut type>

<Clutch type>

Inclined

Inside is shiny without scratches

Smooth all round

Even length

all round

Surface

damaged

Cracked Uneven

thickness

= Improper flaring =

Installation of Indoor Unit

1

Hook the indoor unit onto the upper por-
tion of the installation plate.( engage the
three hooks at the top of the indoor unit
with the upper edge of the installation
plate) Ensure that the hooks are properly
seated on the installation plate by moving
it left and right

2

Unlock the tubing holder from the chassis
and mount between the chassis and instal-
lation plate in order to separate the bottom
side of the indoor unit from the wall.

* The feature can be changed according to the

type of model.

Piping

1

Insert the connecting cable through the
bottom side of indoor unit and connect the
cable (You can see detail contents in
'Connecting the cables' section)

<Left side piping>

View

Terminal block

Connecting cable

Cable retainer

Slide up the metal
plate cover

Installation plate

Tubing Holder

1(L) 2(N) 3(C)

<Left side piping>

<Right side piping>

<Right side piping>

2

Secure the cable onto the control board
with the cable retainer.

3

Tape the tubing pipe, drain hose and the
connection cable. Be sure that the drain
hose is located at the lowest side of the
bundle. Locating at the upper side can
cause overflow from the drain pan through
the inside of the unit.

View

Terminal block

Connecting cable

Cable retainer

Slide up the metal
plate cover

Drain hose

Connecting pipe 

Connecting 
cable

Tape

Drain hose

Connecting pipe 

Connecting 
cable

Tape

Drain hose

1(L) 2(N) 3(C)

7

8

Summary of Contents for AM07BP.NSJ

Page 1: ...he appliance shall be installed in accordance with national wiring regulations Compliance with national gas regulations shall be observed Means for disconnection must be incorporated in the fixed wiring in accordance with the wiring rules If the supply cord is damaged it must be replaced by the man ufacturer or its service agents or similarly qualified person in order to avoid a hazard Appliance s...

Page 2: ...or con sumer purposes not a precision refrigerant system There is risk of damage or loss of property Do not install the unit in potentially explosive atmospheres Refrigerant for R32 Only WARNING The appliance shall be stored in a well ventilated area where the room size corresponds to the room area as specified for operation The appliance shall be stored in a room without continuously operating op...

Page 3: ... Spanner Torque wrench Multi meter Hexagonal wrench Ammeter Gas leak detector Thermometer Level Flaring tool set Name Select the best Location There should not be any heat or steam near the unit Select a place where there are no obstacles around of the unit Make sure that condensation drainage can be conveniently routed away Do not install near a doorway Ensure that the interval between a wall and...

Page 4: ...rrs removal 1 Completely remove all burrs from the cut cross section of pipe tube 2 While removing burrs put the end of the copper tube pipe in a downward direction while removing burrs location is also changed in order to avoid dropping burrs into the tubing Putting nut on Remove flare nuts attached to indoor and outdoor unit then put them on pipe tube having completed burr removal not possible t...

Page 5: ...es according to color codes referring to the wiring diagram NOTE The power cord connected to unit should be selected according to the following national wiring regulations The supply cords of parts of appliances for outdoor use shall not be lighter than polychloroprene sheathed flexible cord code designation 60245 IEC 57 H05RN F CAUTION Outdoor unit 1 Remove the tubing cover from the unit by loose...

Page 6: ...r 2 Connect a field supplied vinyl hose to the drain nipple A If the hose is too long and hangs down fix it carefully to prevent kinks The feature can be changed according to type of model Do not raise Water leakage Tip of drain hose dipped in water Water leakage Ditch Less than 50mm gap Accumulated drain water Air Waving Water leakage B A C 6 6 kW 2 5 3 5 5 0 kW Forming the Piping Form the piping...

Page 7: ...3 Reattach the cover by pushing it back into position If you press and hold the On Off button for 3 5 seconds instead of 6 seconds the unit will switch to the test operation In the test operation the unit blows out strong air for cooling for 18 minutes and then returns to the factory default settings This is performed when the unit is relocated or the refrigerant circuit is serviced Pump Down mean...

Page 8: ...lti model refer to Multi outdoor unit installation manual Capacity kW Pipe Size Standard Length m Max Length Ⓐ m Max Elevation Ⓑ m Additional Re frigerant g m GAS LIQUID mm inch mm inch 2 5 3 5 Ø9 52 3 8 Ø6 35 1 4 7 5 20 10 20 5 0 Ø12 7 1 2 Ø6 35 1 4 7 5 20 10 20 6 6 Ø15 88 5 8 Ø6 35 1 4 7 5 30 15 30 Capacity Mode Indoor temperature Outdoor temperature 2 5 3 5 kW Cooling 18 C 32 C 15 C 48 C Heatin...

Reviews: