Error code
Error name
Error condition
Control during error
Cancel condition
CHxx090
Individual Inletwater temperature sensor error
Individual Inletwater temperature sensor is short/open
Stop applicable cycle
Automatically return to normal condition
CHxx091
Individual Outletwater temperature sensor error
Individual Outletwater temperature sensor is short/open
Stop applicable cycle
Automatically return to normal condition
CHxx104
Communication Error between Outdoor Unit
Communication Error between Outdoor Unit
Stop applicable cycle
Automatically return to normal condition
CHxx105
Fan board communication error
Fan board communication error
Stop applicable cycle
Automatically return to normal condition
CHxx106
Fan PCB IPM fault
Fan PCB IPM fault
Stop applicable cycle
Automatically return to normal condition
CHxx107
Fan DC link low voltage error
Fan DC link low voltage
Stop applicable cycle
Automatically return to normal condition
CHxx113
Liquid pipe temperature sensor error
Liquid temperature sensor is short/open
Stop applicable cycle
Automatically return to normal condition
CHxx114
Sub cooling Suction temperature sensor error
Sub cooling Suction temperature sensor Short/Open
Stop applicable cycle
Automatically return to normal condition
CHxx115
Sub cooling outlet pipe temperature sensor error
Sub cooling outlet pipe temperature sensor Short/Open
Correspond cycle stop