VentilationObjectList
VentilationObjectList
Oneventilationhasthefollowinglistofpoints.Somepointsmaynotbesupporteddependingontheproduct.
Point
Point
Description
Description
ObjectName(_XXX:Address)
ObjectName(_XXX:Address)
Object
Object
Type
Type
Unit
Unit
Text-0
Text-0
Text-1
Text-1
Text-2
Text-2
Text-3
Text-3
Text-
Text-
44
Text-
Text-
55
Text-
Text-
66
1
On/Off(Setting)
StartStopCommand_XXX
BO
-
Stop(0)
Start(1)
-
-
-
-
-
2
On/Off(Status)
StartStopStatus_XXX
BI
-
Stop(0)
Start(1)
-
-
-
-
-
3
Lock(Setting)
LockCommand_XXX
BO
-
Permit
(0)
Prohibit(1)
-
-
-
-
-
4
Lock(Status)
LockStatus_XXX
BI
-
Permit
(0)
Prohibit(1)
-
-
-
-
-
5
FilterSign
FilterSign_XXX
BI
-
Off(0)
On(1)
-
-
-
-
-
6
FilterSignreset
FilterSignReset_XXX
BV
-
-
Reset(1)
-
-
-
-
-
7
OperationMode(Setting)
AirConModeCommand_XXX
MO
-
-
Heat
Exchange
(1)
Auto(2)
Normal
(3)
-
-
-
8
OperationMode(Status)
AirConModeStatus_XXX
MI
-
-
Heat
Exchange
(1)
Auto(2)
Normal
(3)
-
-
-
9
-
-
-
-
-
10 -
-
-
-
-
11 FanSpeed(Setting)
FanSpeedCommand_XXX
MO
-
-
Low(1)
High(2)
Super
High(3)
Auto
(4)
-
-
12 FanSpeed(Status)
FanSpeedStatus_XXX
MI
-
-
Low(1)
High(2)
Super
High(3)
Auto
(4)
-
-
13 SetRoomTemperature
SetRoomTemp_XXX
AV
℃(℉)
16℃~30℃(60℉~86℉)
14 SetTemperature(Status)
RoomTemp_XXX
AI
℃(℉)
15 Alarm
Alarm_XXX
BI
-
Normal
(0)
Abnormal
(1)
-
-
-
-
-
16 ErrorCode
MalfunctionCode_XXX
AI
-
PleaserefertoLGerrorcodelist.
17 UserMode(Setting)
UserModeCommand_XXX
MO
-
-
Quickfresh
(1)
Energy
saving(2)
Clear(3)
-
-
-
18 UserMode(Status)
UserModeStatus_XXX
MI
-
-
Quickfresh
(1)
Energy
saving(2)
Clear(3)
-
-
-
19 RoomTemperature
SetTempStatus_XXX
AI
℃(℉)
16℃~30℃(60℉~86℉)
20
AccumulatedPower
Distribution(Status)
Accumulatedpower(100Watt)_XXX
AI
100
Watt
Wattagevalues
21
ACOperationMode
(Setting)
UserModeAcCommand_XXX
MO
-
-
Cool(1)
Auto(2)
Heat(3)
-
-
-
22 ACOperationMode(Status) UserModeStatus_XXX
MI
-
-
Cool(1)
Auto(2)
Heat(3)
-
-
-
23 ACON/OFF(Setting)
UserModeAcCommand_XXX
BO
-
Stop(0)
Start(1)
-
-
-
-
-
24 ACON/OFF(Status)
UserModeAcStatus_XXX
BI
-
Stop(0)
Start(1)
-
-
-
-
-
25 ACHumidify(Setting)
HumidifierOperCommand_XXX
BO
-
Stop(0)
Start(1)
-
-
-
-
-
26 ACHumidify(Status)
HumidifierOperStatus_XXX
BI
-
Stop(0)
Start(1)
-
-
-
-
-
27
PartialLockAvailable
(Status)
PatialLockAvail_XXX
BI
-
Disabled
(0)
Enabled(1)
-
-
-
-
-
28
SetUpperTemperature
(Setting)
TempRangeUpperLimitCommand_XXX
AV
℃(℉)
18℃~30℃(64℉~86℉)
SetUpperTempaerature
UserManual
UserManual
Summary of Contents for AC Smart 5
Page 1: ...ENGLISH www lg com OWNER S MANUAL GUI AIR CONDITIONER AC Smart 5 M N PACS5A000 Version 1 50 4 ...
Page 16: ...Account You can check the information of the currently logged in account User Manual ...
Page 82: ......
Page 114: ...Usage Mobile Tablet LogIn LogOut Dashboard Device Control Schedule Control User Manual ...