Indoor unit
Compact
6. External pressure setting for
Ceiling concealed duct - Middle static pressure
_
7
Indoor Units
This is the function that decides the strength of the wind for each wind level and because this function is to make the instal-
lation easier.
• If you set ESP incorrectly, the air conditioner may malfunction.
• This setting must be carried out by a certificated-technician.
• Precaution shall be taken not to alter the E.S.P value corresponded to each air flow section.
• E.S.P value can be varied according to the products.
• In the case of going to the next air flow rate stage by pressing the fan-speed button during the setup of the E.S.P value,
the E.S.P value of previous air flow rate will be maintained by remembering the E.S.P value prior to the shift.
How to Set E.S.P. on the remote controller?
TEMP
FAN
SPEED
OPER
MODE
When pressing the button and
button simultaneously for more than 3
seconds, the system will be entered into
the installer setting mode.
- After entering into the installer setting
mode, select the E.S.P code value by
pressing the button.
* E.S.P code value : 03
1
Select the desired air flow rate with
the button. Whenever pressing
the button, [SLO
→
LO
→
MED
→
HI
→
POW] will be indicated.
2
Select the desired air flow rate value
with the temperature up(
▲
), down(
▼
)
button.
* E.S.P value range : 0~255
- E.S.P value will be indicated at the upper
right section of the display window.
3
When pressing the button, currently
established E.S.P value will be set up.
4
When pressing the button and
button simultaneously for more than 3
seconds after the setting has been
completed, the setting mode will be released.
- If there isn’t any button input for more
than 25 seconds, the installer setting
mode will also be released.
5
OPER
MODE
OPER
MODE
FAN
SPEED
FAN
SPEED
OPER
MODE