Ceiling concealed duct - Middle static pressure(2)
_
13
6. External pressure setting for
Indoor unit
Compact
Indoor Units
Model
Step
CMM
Static Pressure[mmAq(Pa)]
2.5(25)
4(39)
5(49)
6(59)
7(69)
8(78)
9(88)
10(98) 11(108) 13(127) 15(147)
Setting Value
32:01
32:02
32:03
32:04
32:05
32:06
32:07
32:08
32:09
32:10
32:11
ABNW30GM1A0
[UM30 N14]
LOW
18.0
96
102
107
104
114
118
122
125
127
132
134
MID
20.0
102
110
114
110
121
125
127
130
133
135
137
HIGH
22.0
110
117
121
118
127
130
133
136
137
138
140
Model
Step
CMM
Static Pressure[mmAq(Pa)]
4(39)
5(49)
6(59)
7(69)
8(78)
9(88)
10(98) 11(108) 12(118) 13(127) 15(147)
Setting Value
32:01
32:02
32:03
32:04
32:05
32:06
32:07
32:08
32:09
32:10
32:11
ABNW36GM2A0
[UM36 N24]
LOW
24.0
88
91
95
100
101
108
113
115
118
118
118
MID
28.0
93
97
101
105
108
115
118
120
124
124
124
HIGH
32.0
101
105
109
112
115
119
123
126
128
128
128
Table 2
1. Be sure to set the value refering table 1. Unexpected set value will cause mal-function.
2. Table 1 is based at 230V. According to the fluctuation of voltage, air flow rate varies.
3. Factory Set(External Static Pressure) each Model
NOTE
Model
Factory set (E.S.P.) mmAq(Pa)
ABNW30GM1A0 [UM30 N14]
6(59)
ABNW36GM2A0 [UM36 N24]
Model
Maximum value
ABNW30GM1A0 [UM30 N14]
120
ABNW36GM2A0 [UM36 N24]
* If it is zero static pressure, please set value below Maximum value.