47 Product Data
Control Device
PTAC
6RWU0-0
5
B
• Remote/Local Control
When remote/local switch #1 is on, it allows the unit to operate by the Remote Wall Thermostat.
The unit control by knobs are not applicable.
• Energy Saver
When the energy saver switch #2 is on, it allows the fan to provide continuous operation in cool or heat modes. When the
switch is off, it allows continuous circulation of room air to provide a balanced temperature in the room.
• Front Desk Control
When the pair wire is connected to the connector FD2 and FD1, the unit can be turned ON or OFF with a switch located at
the Front Desk Control panel. When the front desk switch is ON, the fan operates according to the setting without working
compressor and heater. When the front desk switch is OFF, the unit can operate according to the setting of controls.
Wire # AWG
Maximum Length
#22
600 ft (180 m)
#20
900 ft (270 m)
#18
1500 ft (450 m)
#16
2000 ft (610 m)
FD2 FD1 DR2 DR1 MS2 MS1
Front Desk Control
Front Desk Control
(Molex Housing Spec 396-06V)