![LEYBOLD 230070V02 Operating Manual Download Page 17](http://html1.mh-extra.com/html/leybold/230070v02/230070v02_operating-manual_1890893017.webp)
17
300544652_002_C1 - 11/2016 - © Leybold
4.2 Setpoint relays
The PTR 90 N PENNINGVAC transmitters have up to 3 mechanical relays that can be used for controlling external
process equipment. The relay has closing and breaking contacts and the contacts are rated 30 VDC, 1A resistive
load. For the setup of the setpoints, refer to chapter 6.
Inductive relay load
Special precautions should be taken when driving inductive loads with the relay contact. When an inductive load
like a solenoid is energized, the in-rush current is significant higher than the regular load current. In-rush currents
exceeding the relay contact rating can cause reduction of relay contact life time or contact reliability.
When a solenoid is de-energized, the collapsing magnetic field can cause significant voltage spikes. These spikes
can couple capacitively from cable to cable and interfere with measuring electronics or transmitter signal.
An arc suppression network, as shown schematically to the right, is
recommended. The values of the capacitance C and the resistance R can
be calculated by the following equations:
C = I
2
/(1 x 10
7
)
R = E/ I
a
where:
C is in Farads. R is in ohms
I is DC or AC
peak
load current in amperes. E is DC or AC
peak
source voltage in volts
a = 1 + (50/ E)
Note that R
min
= 0.5 Ω and C
min
= 1×10
-9
F, D is a fast transient suppression diode.
Setpoint functionality
The set point relays can be activated either above or below the set point values. The graphs below show the
different relays stages in either below or above configuration. The NC contact will always be closed in case of
power failure.
Please see the Leybold vacuum transmitter Communication Protocol 300544663 (RS232).
Driving inductive loads via the setpoint relay contacts requires de-energizing spike protection.
Inadequate protection can cause permanent damage to the transmitter or interfere with the analog
output signal.
Always ensure that inductive in-rush currents do not exceed relay contact rating.
When using the setpoint relay to control process equipment always take appropriate precautions to
prevent system damage in case of transmitter power failure. The NC contact will be closed in case
of transmitter power failure.
Critical
!
Critical
!
Summary of Contents for 230070V02
Page 10: ...10 300544652_002_C1 11 2016 Leybold P N 230085V02 P N 230089V02 Flanges KF 25 KF 40 CF 40...
Page 35: ...35 300544652_002_C1 11 2016 Leybold...
Page 36: ...36 300544657_002 10 2015 Leybold Declaration of Conformity...
Page 37: ...37 300544657_002 10 2015 Leybold Notes...
Page 38: ...38 300544657_002 10 2015 Leybold Sales and Service...