14
51D0528
��
��
��
��
��
VENT INSTALLATION
This fireplace must be vented to the outside. The venting system must NEVER be
attached to a chimney serving a separate solid fuel burning appliance. Each gas
appliance must use a separate vent system. Do not use common vent systems.
W
ARNING
Figure 11 - Combustible Clearances for Vent Pipe
COMBUSTIBLE CLEARANCES FOR VENT PIPE
Horizontal sections of this vent system require
a minimum of 3" clearances to combustibles at
the top of the flue and 1" clearance at the sides
and bottom
until the flue penetrates the outside
wall.
A minimum 1" clearance all around the flue
is acceptable at this point of penetration.
Vertical sections of this vent system require a
minimum of 1" clearance to combustibles on all
sides of the pipe.
A Minimum of 3" Clearance
to the Top Is Required Along
Horizontal Length until Flue
Pipe Penetrates Outside Wall.
A Minimum 1"
Clearance to
Combustibles
Permitted All
Around Flue
at Outside
Wall