 ReadySwitch

Prior to Installation: Site Preparation

 

Prepare installation site according to local codes.
The PowerGATE® ReadySwitch™ is to be secured to a building 
using appropriate 3/8“ fasteners (See Figure 1).
The surface where the PowerGATE® ReadySwitch™ is to be 
secured must be capable of supporting the weight of the cabinet 
as well as the cables attached to it.
The following should be taken into consideration when locating 
the PowerGATE® ReadySwitch™:

 

– Identify and meet local codes and local Authority Having 

Jurisdiction (AHJ)

 

– The PowerGATE® ReadySwitch™ is designed for exterior 

operation ONLY

 

– To prevent carbon monoxide poisoning from improperly 

ventilated generator emissions, the PowerGATE® 
ReadySwitch™ must be mounted outdoors only. The 
mounting location is to be carefully selected to allow 
convenient connection to a generator and located a suitable 
distance away from any building openings or HVAC inlets.

 

– Proper clearance must be allowed in front of the 

PowerGATE® ReadySwitch™ to allow for opening of access 
doors and attachment of externally connected cables. This 
distance should be no less than six (6) feet from the face of 
the panel.

Shipment: Unpacking and Inspection

 

– While keylock protection is provided, access by unauthorized 

personnel and vandals should be taken into consideration 
when locating this device.

NOTE:

 Be careful in the use of sharp object when cutting 

packaging as scratching of outer coating may result in rusting.
Perform a visual inspection to ensure the door and handles are in 
functioning condition and that the panel integrity is intact.

Determining Your Part Number

Review Appendix F to verify part number, rating voltage, and 

amperage

Figure 1: 400 AMP

Rear view with mounting holes

Summary of Contents for PowerGATE ReadySwitch

Page 1: ...fety andreliability U S PatentMechanicalInterlockfor safeconnection Utility Generatordisconnects Hingeddoorwithkeylockentry SuitableforuseasService Equipment USOnly LM RS400 Rev 003 ReadySwitch 400 Am...

Page 2: ...ls for Replacement Parts List 11 Appendix E Warning Location 12 Appendix F Specifications Contact Lex Products 800 643 4460 info lexproducts com 2 Important This manual contains information critical t...

Page 3: ...tdoors only The mounting location is to be carefully selected to allow convenient connection to a generator and located a suitable distance away from any building openings or HVAC inlets Proper cleara...

Page 4: ...s only 11 1 4 inches deep Individual cable entry holes restrict access reducing cable theft Enclosure is cULus Listed Type 3R Rainproof Keyed entry prevents unauthorized access and operation Cables dr...

Page 5: ...E Conduit to enter through top or right left side No bottom feed See Figure 5B NOTE To maintain outdoor rating compliance for the enclosure proper sealing procedures must be followed This is to includ...

Page 6: ...Contact Lex Products 800 643 4460 info lexproducts com 6 PowerGATE ReadySwitch Figure 6 Figure 6A Figure 6B...

Page 7: ...A MAIN TERMINAL B BUILDING TERMINAL 8 Replace dead front panel and secure using hardware Place rotation label here Model Rating S N Transfer Switch Accessory Made in USA www lexproducts com 1 800 643...

Page 8: ...vermin door is un obstructed and that the cable can flow freely through cable entry holes 3 Complete the Ground green connections first by feeding the cable through the appropriate port beginning with...

Page 9: ...right Proper disconnection See Figure 9 A Grasp connector jacket firmly and rotate cam connector clockwise until it stops B Firmly pull on connector until it separates from the plug C Set aside 4 Cont...

Page 10: ...d and that cable can flow freely through cable entry holes Ensure that gaskets are pliable and no cracking exists Ensure that door hinges are secure and lubricated Ensure that hasps are intact and ope...

Page 11: ...000 LBL PGIP W1 10519 2 025 LBL PGIP D2 N Manual Transfer Switch This Device Will Not Automatically Transfer ToAn Alternative Source Commutateur Manuel Ce dispositif ne transfert pas automatiquement u...

Page 12: ...wder Coated Steel ANSI 61 Grey Dimensions 48 x30 x13 5 48 x30 x13 5 Approximate Weight 252 lbs 252 lbs Part Number PIPM0400 C C AJ GBXEE PIPM0400 S S AJ GBXFF Rating 400 Amp 3 Phase H H H N G 4 Pole 5...