Contact Lex Products:    800.643.4460   [email protected]

11

PowerGATE

®

 ReadySwitch

p/n: – 10519-2-024

p/n: – 10519-2-023

10519-2-023

10519-2-026

LBL RDYSWNSE-SW 

For Service Entrance Rated Version please use 

p/n: LBL-RDYSW-SCCR-BRK

Appendix E

Warning Locations

GN

L1

L2

L3

UTILITY

GENERATOR

ON

TRANSFER SWITCH AND

INLET PANEL

READYSWITCH

TM

T

Not for indoor use

Continuous load current not to exceed 80 percent of switch rating

Suitable only  for use with generators that do not have the neutral bonded

to the ground or the generator frame

Installation of the temporary wiring shall be performed according to the

applicable electrical codes

Temporary cable shall be suitable for hard usage, in wet or outdoor applications

Strain relief shall be provided for a connection with a vertical unsupported

length of 2 meters or more

For power inlet use only. Not for use as an outlet.

OFF

ON

OFF

WARNING

AVERTISSEMENT

Risk of Electric Shock

Plug connection should be in the following order:

1) Equipment grounding conductor connectors,

2) Grounded circuit conductor connectors, and

3) Ungrounded conductor connectors.

Disconnection should be in the reverse order

Risque de choc électrique

Le raccordement devrait être effectué dans l’ordre qui suit:

1) Conducteur de mise à la terre de l’appareillage

2) Conducteur du circuit mis à la terre

3) Conducteurs non mis à la terre

La mise hors tension doit se faire dans l’ordre inverse

LBL-PGIP-W

1

Type 3R une fois installé  avec conduit ou raccords de conduits à l'épreuve de la pluie (homologation UL)

Ne pas utiliser à l’intérieur

Le courant de charge continu ne doit pas dépasser de 80 pourcent le courant nominal du commutateu r

Approprié seulement pour utilisation avec des générateurs dont le neutre n'est pas mis à la terre ou au  

châssis du générateur.

L'installation du câblage temporaire doit être effectuée conformément aux codes de l'électricité applicable s

Un câble temporaire devra être approprié pour une utilisation dans des applications à l'extérieur ou 

dans un environnement humide, avec une gaine robuste.

Un collier devra être fourni pour une connexion avec une longueur verticale non supportée 

de deux mètres ou plus.

DANGER

Do not start the generator until all connectors are connected

or made to be inaccessible. Any terminal may be energized

when any cable is connected. De-energize cables at the

generator prior to connecting or removing any connectors

Ne pas mettre la génératrice en marche avant que tous les

connecteurs soient connectés ou rendus inaccessibles.

N’importe quelle borne peut être mise sous tension si un

câble est raccordé. Débrancher les câbles à la génératrice

avant de brancher ou de débrancher les connecteurs

LBL-PGIP-D

2

More than one live circuit: 

Disconnect all sources before servicing

Plus d’un circuit sous tension:

Débrancher toutes les sources d’alimentation avant

d’entreprendre le dépannage

WARNING

AVERTISSEMENT

10519-2-025 rev 00

0

LBL-PGIP-W1

10519-2-025

LBL-PGIP-D2

N

Manual Transfer Switch – This Device

Will Not Automatically Transfer To An Alternative

Source
Commutateur Manuel – Ce dispositif 

ne transfert pas automatiquement 

une charge vers une source auxiliaire

CAUTION

ATTENTION

10519-2-024 rev 000

TRANSFER SWITCH AND

INLET PANEL

TM

READYSWITCH

10519-2-023 rev 000

Verify the condition of the power source prior to

manually transferring. Manual operation may result in

out-of-phase transfer when both sources are energized.

Vérifiez l'état de la source d'alimentation avant 

d'effectuer le transfert manuellement. Un  fonctionne-

-ment manuel risquerait de causer un  transfert hors 

phase lorsque les deux sources sont activées.

WARNING

AVERTISSEMENT

10519-2-026 rev 000

10519-2-024

Manual Transfer Switch – This Device

Will Not Automatically Transfer To

 

An Alternative

Source

Commutateur Manuel – Ce dispositif 

ne transfert pas automatiquement

 

une charge vers une source auxiliaire

CAUTION

ATTENTION

10519-2-024 rev 00

0

 

p/n: – LBL-RDYSW-SCCR-SW

For Service Entrance Rated Version please use 

Part Number: LBL-RDYSW-SCCR-SW

GG

N

LBL-RDYSW-GGN 000

LBL-RDYSW-BUILDING 000

L1

L2

L3

BUILDING (LOAD)

UTILITY: 43 N-M, 380 IN-LBs

3/16”

BUILDING, N, G: 42 N-M, 375 IN-LBs

8 mm

Cu – Al

75°C / 90°C

LBL-RDYSW-TSS 000

L2

UTILITY (LINE)

L1

L3

LBL-RDYSW-UTILITY 000

p/n: – LBL-RDYSW-TSS

p/n: – LBL-RDWSW-UTILITY

p/n: – LBL-RDYSW-GGN

p/n: LBL-RDYSW-BUILDING

Model
Rating

S/N

Made in USA    

www.lexproducts.com    1-800-643-4460

Fabriqué aux Etats-Unis

Suitable for use as service equipment in the USA only.

Peut être utilisé comme appareillage de branchement

aux Etats-Unis seulement.

E465545

 TYPE 3R 

RAINPROOF

Transfer Switch / Commutateur

LBL-RDYSW-3R 000

Appendix D 

(continued)

SHORT-CIRCUIT WITHSTAND AND CLOSING RATINGS

COURANTS NOMINAUX DE RÉSISTANCE AU COURT-CIRCUIT ET DE FERMETURE DE CIRCUIT 

When protected by a circuit breaker, this transfer switch is suitable for use in a circuit capable of 

delivering the short-circuit current for the maximum time duration and voltage marked below.

S’il est protégé par un disjoncteur, ce commutateur convient aux circuits capables d’acheminer 

un courant de court-circuit pendant la durée et à la tension maximales indiquées plus bas.. 

SHORT-CIRCUIT CURRENT

COURANT DE COURT-CIRCUIT 

VOLTAGE MAXIMUM

TENSION MAXIMUM

480V AC

This transfer switch does not include short-time current ratings. 400A maximum overcurrent devicew

Ce commutateur n’est pas évalué pour les courants nominaux de courte durée.

400A maximum le dispositif de protection

35,000 A RMS

The circuit breaker must include an instantaneous trip response and shall not include a short-time

trip response.

Le disjoncteur doit être à déclenchement instantané sans déclenchement rapide.

The maximum clearing time of the instantaneous trip response must be equal to or less than the time

 duration shown for the marked short-circuit current.

Le temps de coupure maximal pour le déclenchement instantané doit être égal ou  inférieur à la durée

 indiquée pour le courant de court-circuit.

TIME DURATION

LE TEMPS DURÉE

0.050 S

600V AC

25,000 A 

LBL-RDYSW-SCCR-SW 000

0.050 S

RMS

Summary of Contents for PowerGATE ReadySwitch

Page 1: ...fety andreliability U S PatentMechanicalInterlockfor safeconnection Utility Generatordisconnects Hingeddoorwithkeylockentry SuitableforuseasService Equipment USOnly LM RS400 Rev 003 ReadySwitch 400 Am...

Page 2: ...ls for Replacement Parts List 11 Appendix E Warning Location 12 Appendix F Specifications Contact Lex Products 800 643 4460 info lexproducts com 2 Important This manual contains information critical t...

Page 3: ...tdoors only The mounting location is to be carefully selected to allow convenient connection to a generator and located a suitable distance away from any building openings or HVAC inlets Proper cleara...

Page 4: ...s only 11 1 4 inches deep Individual cable entry holes restrict access reducing cable theft Enclosure is cULus Listed Type 3R Rainproof Keyed entry prevents unauthorized access and operation Cables dr...

Page 5: ...E Conduit to enter through top or right left side No bottom feed See Figure 5B NOTE To maintain outdoor rating compliance for the enclosure proper sealing procedures must be followed This is to includ...

Page 6: ...Contact Lex Products 800 643 4460 info lexproducts com 6 PowerGATE ReadySwitch Figure 6 Figure 6A Figure 6B...

Page 7: ...A MAIN TERMINAL B BUILDING TERMINAL 8 Replace dead front panel and secure using hardware Place rotation label here Model Rating S N Transfer Switch Accessory Made in USA www lexproducts com 1 800 643...

Page 8: ...vermin door is un obstructed and that the cable can flow freely through cable entry holes 3 Complete the Ground green connections first by feeding the cable through the appropriate port beginning with...

Page 9: ...right Proper disconnection See Figure 9 A Grasp connector jacket firmly and rotate cam connector clockwise until it stops B Firmly pull on connector until it separates from the plug C Set aside 4 Cont...

Page 10: ...d and that cable can flow freely through cable entry holes Ensure that gaskets are pliable and no cracking exists Ensure that door hinges are secure and lubricated Ensure that hasps are intact and ope...

Page 11: ...000 LBL PGIP W1 10519 2 025 LBL PGIP D2 N Manual Transfer Switch This Device Will Not Automatically Transfer ToAn Alternative Source Commutateur Manuel Ce dispositif ne transfert pas automatiquement u...

Page 12: ...wder Coated Steel ANSI 61 Grey Dimensions 48 x30 x13 5 48 x30 x13 5 Approximate Weight 252 lbs 252 lbs Part Number PIPM0400 C C AJ GBXEE PIPM0400 S S AJ GBXFF Rating 400 Amp 3 Phase H H H N G 4 Pole 5...