i Series i24, i24e, & quad Installation Supplement 

 

Page 3 of 3 

LIT-30955-02 
 

 
 

 

Breaker with Fluorescent Breaker Handle Tie 

Kit Installed 

 

Luma -Net  Termination 

Luma-Net Control Signal Installation Requirements 

For i Series e dimmer racks which require the termination of a Luma-Net control run, follow 
these instructions. 
 
Connection 
The Luma-Net link connects to the backplane of the rack on 
TB1 as follows: 
 

Signal 

Luma -Net 3 

Terminal 

Rack 

Terminal 

Rack Label 

Rem + 

RAKCOM 

Rem - 

10 

RAKCOM 

overlined 

Common 

GND 

+V 

+12V 

 
Although most Luma-Net phoenix style connectors have six 
terminals, there is no terminal 5 nor terminal 6 connection at 
the dimmer rack.  Terminal 6 which is used for the hardware 
lock feature has no use at the dimmer rack and the 
“terminate” feature which is handled by terminal 5 is 
handled by the termination jumper. 
 
Termination 
If the rack is at the end of the run, Jumper JP2 (Rackcom Termin.) must be installed in the 
backplane to terminate the run. The jumper is shipped installed by factory default. 
 
Now the dimmer rack is capable of receiving and processing Luma-Net commands. 
 

Special Installation Requirements for HiLume Dimming Circuits

 

The HILUME feature is only usable in i Series e. This 
style of fluorescent dimming ballast requires (3) wires, (1) 
switched, (1) dimmed, and (1) neutral.  To accommodate 
these requirements, the software will couple the odd-
numbered dimmer with the next even-numbered dimmer. 
The odd-numbered dimmer is the variable component and 
the even-numbered dimmer is the switched component. 
The breakers for these dimmers must be tied together with 
the CTP-4-0307 fluorescent handle-tie kit and the rack 
slot labeled. Installation instructions for this are included 
with the kit. 
 
The odd/even breakers in the i Series Quad are not below each other so they cannot be tied 
together; therefore, HILUME is not a quad feature. When the HILUME feature couples the 
dimmers the second address is dropped unless the subsequent addresses are moved up dimmer by 
dimmer. For this reason it is a good idea to put the HILUME dimmers at the end. 
 