* Sensor with “S“ type output, for each flash of the LED switches its output on for approx. 3 ms. This period is
sufficiently short to avoid unwanted switching of relay contacts. For binary inputs, we recommend to set the filter so
as not to respond to pulses shorter than 3 ms.
Indicator
Function
Orange LED
Continuous light
– Sensor is closed (switched ON)
Dark
– Sensor is open (switched OFF)
Rapid lashing
(period 0.2 sec.)
*
– Unrecognized upper and lower limits of setting mistake
Slow lashing
(period 0.8 sec.)
– Short circuit at sensor output
S
TaTuS
-
Sensing
b)
7
Put the level of the measured medium in the state
above the upper edge
of the
sensor in the tank or in the gauge-pipe.
Attach the magnetic pen MP-8 to the sensitive spot
M
for
maximum 2 seconds
.
When the LED goes out, the sensor is in the state open.
After removal of the magnetic pen check the status of orange lights:
If the LED lights or is flashing rapidly (0.2 s), go to step 4.
If the LED doesn´t light, you must repeat step 2 so as to observe the limit
of 4 seconds attaching magnetic pen.
If the LED doesn´t light, settings of the sensor is correct.
If the LED lights, the sensor was set incorrectly and you must repeat the
procedure from step 1.
If the LED is flashing, the sensor didn´t recognize upper and lower limits.
In this case, first verify that at the step 1 the level of the measured medium
was below the lower edge of the sensor and at the step 3 the level of the
measured medium was above the upper edge of the sensor. Then make sure
that the thickness of the gauge-pipe wall or the tank wall does not exceed
the limit specified in the Technical specifications (p. 2). If not, check there
isn´t a thick layer of sediment on the inner wall of the tank or the gauge-pipe.
1.
2.
3.
4.
5.
6.
Mode C
(normally closed)
Put the level of the measured medium in the state
below the lower edge
of the
sensor in the tank or in the gauge-pipe.
Attach the magnetic pen
PM-8
o
n
the sensitive spot
M
for
minimum 4
seconds
. When the LED lights up, the sensor is in the state closed.
Afte
r removal of the magnetic pen check the status of orange lights:
-
-
-
-
-
After this settings the sensor responds to the level immersion and emersion in the
upper half of the sensing area and the
hysteresis
size 5 mm (1/8 of the distance
between the bottom and the top of the sensor).