6

Sensitive spot

3.

 

S

ENSOr

 

SETTiNgS

The setting is done by placing of magnetic pen 

PM-8

 to sensitive spot 

M

 

located on the front of 

the sensor. Short time  attaching (up to 2 sec.) 

of the magnetic pen to the sensitive spot

 

M

 

makes 

the sensor open. Long attach (at least 

4 sec.) 

of 

 

the 

 

pen 

 

when 

 

the 

 

level 

 

is 

 

changed, 

 

defines 

 

closed state of the sensor. In this way the sensiti-

vity for the measured medium and switching modes 

O

“ (normally open) or “

C

“ (normally closed) is set. 

When changing the fluid it is necessary to make 

the new setting.

a) Mode O 

(normally open) 

Put the level of the measured medium in the state 

below the lower edge

 of the 

If the LED doesn´t light or is flashing rapidly (0.2 s), go to step 4.

If the LED lights, you must repeat step 2 so as not to exceed the limit of 2 

seconds  attaching  magnetic  pen. 

If the LED lights, settings of the sensor is correct.  

If the LED doesn´t light, the sensor was set incorrectly and you must repeat 

the procedure from step 1.

If the LED is flashing, the sensor didn´t recognize upper and lower limits.               

In this case, first verify that at the step 1 the level of the measured medium 

was below the lower edge of the sensor and at the step 3 the level of the 

measured medium was above the upper edge of the sensor. Then make sure 

that the thickness of the gauge-pipe wall or the tank wall does not exceed 

the limit specified in the Technical specifications (p. 2). If not, check there 

isn´t  a  thick  layer  of  sediment  on  the  inner  wall  of  the  tank  or  the  gauge-pipe.                                                                                                            

1.

2.

3.                         

4.

5.

6.

sensor in the tank or in the gauge-pipe.

Attach the magnetic pen 

PM

-8 to the sensitive spot 

M

 

for 

maximum 2 seconds

When the LED goes out, the sensor is in the state open.

Afte                               

r removal of the magnetic pen check the status of orange lights:                                                     

-

-

Put the level of the measured medium in the state 

above the upper edge

 of the 

sensor in the tank or in the gauge-pipe.

Attach the magnetic pen 

PM

-8 to the sensitive spot 

M

 

for 

minimum 4 seconds

.       

When the LED lights up, the sensor is in the state closed.

Afte                               

r removal of the magnetic pen check the status of orange lights:

-

-

-

For security reasons, we recommend to set the mode O (normally open, sensor closes 

when immersed) for minimum level detection. Any failure of the sensor or wiring is equally 

apparent as the emergency level state. Analogously – for the maximum level detection 

is recommended to set the mode C (normally closed, sensor opens when immersed).

Summary of Contents for NC30-10

Page 1: ...shed in this manual before the rst use of the sensor Keep the manual at a safe place The manufacturer reserves the right to implement changes without prior notice INSTRUCTION MANUAL industrial electro...

Page 2: ...s 3 Recommended range of application 4 Unsuitable range of application 4 Procedure for put sensor into operation 4 1 Installation 4 2 Electrical connection 5 3 Sensor settings 6 Status signalization 7...

Page 3: ...Switching current Min Max Output type P open collector PNP Output type S two wire el switch 100 mA 3 3 40 mA Remanent voltage ON state Output type P open collector PNP Output type S two wire el switch...

Page 4: ...cable LED Electrode Sensitive spot for setting Detection of various types of liquids water disel oil cooling liquids water solutions some types of solvents It is suitable for glass or plastic gauge p...

Page 5: ...the detec ted medium see technical data the maximum is 8 mm The sensor is fixed to the gauge pipe or tube by means of two plastic straps 2 5 mm width The cable should be vertically down wards oriented...

Page 6: ...ype output Positive pole U of power supply is connected to brown wire or pin connector No 1 negative pole is connected to blue wire or pin connector No 3 Load relay is connec ted to black wire or pin...

Page 7: ...he measured medium was below the lower edge of the sensor and at the step 3 the level of the measured medium was above the upper edge of the sensor Then make sure that the thickness of the gauge pipe...

Page 8: ...light settings of the sensor is correct If the LED lights the sensor was set incorrectly and you must repeat the procedure from step 1 If the LED is flashing the sensor didn t recognize upper and low...

Page 9: ...rode polarity overvoltage and short term current overload on the output Electromagnetic compatibility is provided by conformity with standards SN EN 55022 B SN EN 61326 1 SN EN 61000 4 2 SN EN 61000 4...

Page 10: ...es outlined above 2 have been subjected to electrical mechanical or chemical damage due to improper accidental or negligent use 3 have been modified or altered 4 anyone other than service personnel au...

Page 11: ...ICON PROCESS CONTROLS Corrosion Free Liquid Process Instrumentation Equipment Flow Level Pressure Temperature...