6
Sensitive spot
3.
S
ENSOr
SETTiNgS
The setting is done by placing of magnetic pen
PM-8
to sensitive spot
M
located on the front of
the sensor. Short time attaching (up to 2 sec.)
of the magnetic pen to the sensitive spot
M
makes
the sensor open. Long attach (at least
4 sec.)
of
the
pen
when
the
level
is
changed,
defines
closed state of the sensor. In this way the sensiti-
vity for the measured medium and switching modes
“
O
“ (normally open) or “
C
“ (normally closed) is set.
When changing the fluid it is necessary to make
the new setting.
a) Mode O
(normally open)
Put the level of the measured medium in the state
below the lower edge
of the
If the LED doesn´t light or is flashing rapidly (0.2 s), go to step 4.
If the LED lights, you must repeat step 2 so as not to exceed the limit of 2
seconds attaching magnetic pen.
If the LED lights, settings of the sensor is correct.
If the LED doesn´t light, the sensor was set incorrectly and you must repeat
the procedure from step 1.
If the LED is flashing, the sensor didn´t recognize upper and lower limits.
In this case, first verify that at the step 1 the level of the measured medium
was below the lower edge of the sensor and at the step 3 the level of the
measured medium was above the upper edge of the sensor. Then make sure
that the thickness of the gauge-pipe wall or the tank wall does not exceed
the limit specified in the Technical specifications (p. 2). If not, check there
isn´t a thick layer of sediment on the inner wall of the tank or the gauge-pipe.
1.
2.
3.
4.
5.
6.
sensor in the tank or in the gauge-pipe.
Attach the magnetic pen
PM
-8 to the sensitive spot
M
for
maximum 2 seconds
.
When the LED goes out, the sensor is in the state open.
Afte
r removal of the magnetic pen check the status of orange lights:
-
-
Put the level of the measured medium in the state
above the upper edge
of the
sensor in the tank or in the gauge-pipe.
Attach the magnetic pen
PM
-8 to the sensitive spot
M
for
minimum 4 seconds
.
When the LED lights up, the sensor is in the state closed.
Afte
r removal of the magnetic pen check the status of orange lights:
-
-
-
For security reasons, we recommend to set the mode O (normally open, sensor closes
when immersed) for minimum level detection. Any failure of the sensor or wiring is equally
apparent as the emergency level state. Analogously – for the maximum level detection
is recommended to set the mode C (normally closed, sensor opens when immersed).