Starting up the device - Configuration
Leuze electronic
BCL 604i
61
Output data length
1 byte consistent
Data reset behavior:
If the data reset control bit is activated, the following actions are carried out:
1. Deletion of decoding results that may still be stored.
2. Reset of module 13 - fragmented read result (see chapter 10.7.4), i.e., even a partially transmitted
read result is deleted.
3. Deletion of the input data areas of all modules. Exception: The input data of module 60 - device sta
-
tus (see chapter 10.11.1) is not deleted. For the status byte of decoding result modules 20 … 27
(see chapter 10.8.2), the two toggle bytes and the reading gate status remain unchanged.
10.7.2 Module 11 – Reading gate control
Description
With the module, the reading gate control of the bar code reader can be adapted to the application. With
different parameters from the bar code reader, a time-controlled reading gate may be created. In addition,
it defines the internal criteria for the reading gate end and the completeness inspection.
Data reset
Deletes decoding results that may have been
stored and resets the input data of all modules.
0.5
Bit
0 -> 1: Data reset
0
-
Free
0.6
Bit
Free
0.7
Bit
Output data
Description
Addr.
Data type
Value range
Init value Unit
If several bar codes are decoded in sequence without the acknowledge mode having been acti
-
vated, the input data of the result modules are overwritten with the respective most recently read
decoding result. If a data loss in the control is to be avoided in such a case, mode 1 (with Ack)
should be activated. If multiple decoding results occur within one reading gate, it is possible - de
-
pendent on the cycle time - that only the last decoding result is visible on the bus. In this case,
the acknowledge mode MUST be used. There is otherwise a risk of data loss. Multiple, individual
decoding results may occur within one reading gate if module 12 – Multi-label (see
chapter 10.7.3) or one of the identifier modules (see chapter 10.10) is used.