Display and control panel AMS 307i
Leuze electronic GmbH + Co. KG
AMS 307
i
45
TNT
35/7-2
4V
SSI submenu
Position value submenu
Table 8.2:
SSI submenu
Level 3
Level 4
Level 5
Selection/configuration option
Description
Standard
Activation
ON/OFF
Activates or deactivates the AMS 307
i
as an SSI participant.
ON
Encoding
Binary/gray
Specifies the output format of the measurement value.
Gray
Number of
data bits
24-bit/25-bit/26-bit
The measurement value can be represented on the SSI inter
-
face in this data width.
24 bit
SSI resolution
0.001mm / 0.01mm / 0.1mm / 1mm / 10mm / free resolu
-
tion
The measurement value can be displayed in these resolu
-
tions.
0.1mm
Error bit
ON/OFF
This parameter determines whether an error bit is also
attached to the "number of data bits". The error bit is the LSB
and is not converted in the case of gray representation of the
measurement value.
ON
Error bit func
-
tion
The error bit can be assigned the following status messages:
Overflow / Intensity (ATT) / Temperature (TMP) /
Laser (LSR) / Plausibility (PLB) / Hardware (ERR).
In the case of multiple entries, the individual states in the error
bit are processed in an OR function.
Plausibil
-
ity (PLB)
Hardware
(ERR)
Update rate
1.7 / 0.2ms
1.7
Clock fre
-
quency
50 - 79kHz / 80 - 800kHz
Selection of the clock frequency.
80 -
800kHz
Table 8.3:
Position value submenu
Level 3
Level 4
Level 5
Selection/configuration option
Description
Standard
Unit
Metric/Inch
Specifies the units of the measured distances
Metric
Counting
direction
Positive/Negative
Positive: The measurement value begins at 0 and increases
with increasing distance.
Negative: The measurement value begins at 0 and decreases
with increasing distance. Negative distance values may need
to be compensated with an offset or preset.
Positive
Offset
Output value = measurement value + offset
The resolution of the offset value is independent of the
selected "Position resolution" and is entered in mm or inch/
100. The offset value is effective immediately after entry. If the
preset value is activated, this has priority over the offset. Pre
-
set and offset are not offset against each other.
0 mm
Preset
The preset value is accepted by means of teach pulse. The
teach pulse can be applied to a hardware input of the M12
PWR connector. The hardware input must be appropriately
configured. See also configuration of the I/Os.
0 mm