Leuze electronic MSI-MD-FBX Original Operating Instructions Download Page 36

Diagnostics and troubleshooting

Leuze electronic

MSI-MD-FBX

36

11

Diagnostics and troubleshooting

11.1

What to do in case of failure?

After switching on the muting controller, the display elements (see chapter 3.2 "Display elements") assist in
checking the correct functionality and in fault-finding.

In case of failure, you can read a message from the 7-segment display. With the error message you can
determine the cause of the error and initiate measures to rectify it.

NOTICE

If the light curtain responds with an error display, you will often be able to eliminate the
cause yourself!

Ä

Switch off the machine and leave it switched off.

Ä

Analyze and eliminate the cause of the fault using the following table.

Ä

If you are unable to rectify the fault, contact the Leuze electronic branch responsible for you
or call the Leuze electronic customer service (see chapter 12 "Service and support").

With the 

Sensor Studio

 diagnostics software, you can create a service file that you can send to Leuze elec-

tronic customer service in the event of service requests (Diagnostics software Sensor Studio). The service
file contains all available information on the muting controller, as well as configuration and settings.

11.2

Error messages 7-segment display

User messages/notes and error messages are indicated by the alternating display of a letter and a two-digit
number.

Tab. 11.1: 

Messages of the 7-segment display (F: internal device error, E: external error, U: usage info during appli-
cation errors)

Error

Cause/description

Remedies and measures

Behavior of the
muting controller

F[No. 0-255]

Internal error

In the event of an unsuccessful
restart, contact customer service.

OFF

Very high overvoltage (± 40 V) Supply the device with the correct

voltage.

E01

Cross connection between
OSSD1 and OSSD2

Check the wiring between OSSD1
and OSSD2.

Automatic reset

E02

Overload on OSSD1

Check the wiring or exchange the
connected component (reducing
the load).

Automatic reset

E03

Overload on OSSD2

Check the wiring or exchange the
connected component (reducing
the load).

Automatic reset

E04

High-impedance short circuit to
VCC OSSD1

Check the wiring. Exchange the
cable, if applicable.

Automatic reset

E05

High-impedance short circuit to
VCC OSSD2

Check the wiring. Exchange the
cable, if applicable.

Automatic reset

E06

Short circuit against GND at
OSSD1

Check the wiring. Exchange the
cable, if applicable.

Automatic reset

E07

Short circuit a24 V at
OSSD1

Check the wiring. Exchange the
cable, if applicable.

Automatic reset

E08

Short circuit against GND at
OSSD2

Check the wiring. Exchange the
cable, if applicable.

Automatic reset

E09

Short circuit a24 V at
OSSD2

Check the wiring. Exchange the
cable, if applicable.

Automatic reset

Summary of Contents for MSI-MD-FBX

Page 1: ...I M P L E M E N T A T I O N A N D O P E R A T I O N O r i g i n a l o p e r a t i n g i n s t r u c t i o n s EN 2017 03 50136367 We reserve the right to make technical changes MSI MD FBX Muting Cont...

Page 2: ...2017 Leuze electronic GmbH Co KG In der Braike 1 D 73277 Owen Germany Phone 49 7021 573 0 Fax 49 7021 573 199 http www leuze com info leuze de Leuze electronic MSI MD FBX 2...

Page 3: ...knowledging resetting 17 5 Applications 18 5 1 Access guarding with timing controlled muting 18 6 Mounting 19 6 1 Mounting the muting controller 19 6 1 1 Mounting in the UDC device column 19 6 1 2 Mou...

Page 4: ...he operator 34 9 3 1 Checklist periodically by the operator 34 10 Care maintenance and disposal 35 11 Diagnostics and troubleshooting 36 11 1 What to do in case of failure 36 11 2 Error messages 7 seg...

Page 5: ...ds Symbol indicating dangers to persons Symbol indicating possible property damage NOTE Signal word for property damage Indicates dangers that may result in property damage if the measures for dan ger...

Page 6: ...s Failure Muting Temporary automatic suppression of the safety functions OSSD Safety related switching output Output Signal Switching Device PFHd Probability of a dangerous failure per hour Probabilit...

Page 7: ...against being restarted Only have work on the electrical system and electronics performed by a competent person see chapter 2 2 Necessary competencies 2 1 1 Intended use WARNING A running machine may...

Page 8: ...es Applications in explosive or easily flammable atmospheres On machines or systems with long stopping times 2 2 Necessary competencies The safety relay may only be configured installed connected comm...

Page 9: ...pe and content of all imparted information must not lead to unsafe actions by users The manufacturer of the machine is responsible for Safe machine construction Safe implementation of the safety relay...

Page 10: ...24 V supply voltage The following safety sensors from Leuze electronic are released for connection to the muting controller Safety light barriers of the MLD series Safety light curtains of the MLC se...

Page 11: ...ring the muting function and the Micro USB connection for reading out diagnostics 3 7 segment display 4 Connection for the safety sensor 5 Connection for acknowledgment unit 6 Connections for muting s...

Page 12: ...muting controller is equipped with the following display elements LED indicators for the status of the assigned input signals 1 3 2 7 4 9 11 10 5 8 11 6 1 PWR LED 2 OSSD LED 3 RI LED 4 ERR LED 5 SC LE...

Page 13: ...C LG OFF OSSDs of the safety sensor in the OFF state Green OSSDs of the safety sensor in the ON state 8 ML Blue Muting indicators OFF no muting active Continuous light muting active safety sensor is b...

Page 14: ...g controller as muting sen sors see chapter 14 Order guide and accessories The state of a muting sensor is transferred on pin 4 of the connection on the muting controller The muting signals of the mut...

Page 15: ...muting sensors 4 1 1 Timing controlled 2 sensor muting with Muting enable With the muting enable function muting is enabled or disabled via an external muting enable signal The muting enable function...

Page 16: ...nded No muting signal is activated Muting is ended immediately even if the acknowledgment unit is not released Muting controller with muting enable a muting signal is activated Muting is initiated whe...

Page 17: ...eadyForReset signal signals via the RES LED that the system is waiting for actuation of the acknowl edgment unit reset button The RES LED illuminates red if the OSSDs of the safety sensor are switched...

Page 18: ...plications 5 1 Access guarding with timing controlled muting 3 2 1 4 1 Safety sensor 2 Muting controller 3 Muting sensors 4 Acknowledgment unit Fig 5 1 Access guarding with timing controlled muting fo...

Page 19: ...controller You can mount the muting controller as follows Mount in the UDC device column of the receiver of the safety sensor Mount on the UDC device column of the receiver of the safety sensor Mount...

Page 20: ...ing sensors This information must be observed when mount ing the muting sensors WARNING Improper installation may result in serious injury If the distance between transmitter and receiver is larger th...

Page 21: ...beam paths intersect behind the protective field within the danger zone Diffuse sensors that scan along the side of the transport material make sure scanning range is set cor rectly A photoelectric se...

Page 22: ...Muting sensor 1 MS2 Muting sensor 2 S Minimum distance between the protective field of the AOPD and the detection points of the muting sensor light beams a b Distance between muting object and other f...

Page 23: ...m Arrangement of diffuse sensors An additional option for arranging the muting sensors is shown in the following figure The diffuse sensors are arranged and set within the danger zone so that their sc...

Page 24: ...ensors so that the intersection point of their light beams is at the same height or higher than the lowest light beam of the safety sensor This prevents or hinders manipulation with the feet since the...

Page 25: ...d signal lines within the electrical installation space or perma nently in cable ducts Lay the cables and lines so that they are protected against external damages For further information see EN ISO 1...

Page 26: ...Connections for muting sensors Fig 7 1 Muting controller connections Connect the muting controller to the machine interface see chapter 7 2 Pin assignment of the ma chine interface Connect the safety...

Page 27: ...T 24 V if OSSD1 of the muting controller is active 6 Pink OSSD2 OUT 24 V if OSSD2 of the muting controller is active 7 Blue 0 V Supply voltage 8 Red M EN TO IN Signal muting enable muting timeout FE H...

Page 28: ...acknowledgment unit 3 Blue GND Supply voltage 4 Black Reset IN Switching signal reset 5 Gray n c This pin is not contacted at the device FE Housing of the M12 socket FE functional earth shield 7 5 Pin...

Page 29: ...4 4 5 5 1 MS4 1 MS3 2 2 3 3 4 4 5 5 1 ML 1 RES S1 H1 H1 2 2 3 3 4 4 5 5 1 SC 1 LC LG 2 2 3 3 4 4 5 5 6 7 8 Schaltsignal BN SH OSSD2 VIN2 5 GND electronic BK RD A2 Muting aktiv V 4 2 V 4 2 2 4 WH 2 Sc...

Page 30: ...nterface signal Manually via acknowledgment unit 5 Muting enable With muting enable Without muting enable 6 Muting timeout With muting timeout extension Without muting timeout extension Procedure Disc...

Page 31: ...itch off When configuring make certain that the switch position is identical in both DIP switch blocks 1 2 3 4 5 6 7 8 A B 1 1 2 2 A DIP switch block A B DIP switch block B 1 Switch position ON 2 Swit...

Page 32: ...ting of DIP switches If a DIP switch configuration is set that does not correspond to that of a permissible operating mode an operating mode error is triggered and the OSSDs switch off Only set one of...

Page 33: ...be performed by qualified persons see chapter 2 2 Necessary competencies in the following situations Prior to initial commissioning Following modifications to the machine After longer machine downtime...

Page 34: ...ter and receiver of the safety sensor and when using de flecting mirrors a second person may be necessary WARNING Unpredictable machine behavior during the test may result in serious injury Make certa...

Page 35: ...s such as thinner or acetone for cleaning the device Use of improper cleaning agents can damage the 7 segment display Maintenance The device does not normally require any maintenance by the operator R...

Page 36: ...notes and error messages are indicated by the alternating display of a letter and a two digit number Tab 11 1 Messages of the 7 segment display F internal device error E external error U usage info d...

Page 37: ...Acknowledgment unit E80 Invalid operating mode Check the configuration of the op erating mode and restart Locking E87 Operating mode changed Check the configuration of the op erating mode and restart...

Page 38: ...g sensors Automatic reset U48 Sequence error between mut ing sensor 3 and muting sen sor 2 Check the arrangement and align ment of the muting sensors Automatic reset U49 Sequence error between mut ing...

Page 39: ...66 Sequence error Check the connection of the mut ing sensors Automatic reset U67 No muting enable signal be fore start of muting Activate muting enable before muting Automatic reset U73 Restarting th...

Page 40: ...D FBX 40 12 Service and support 24 hour on call service at 49 7021 573 0 Service hotline 49 7021 573 123 E mail service protect leuze de Return address for repairs Servicecenter Leuze electronic GmbH...

Page 41: ...tion necessary at 20 ms voltage dip min 250 mA external load Residual ripple of the supply voltage 5 within the limits of Uv Current consumption 150 mA without load Protection class III Degree of prot...

Page 42: ...ection 0 25 mm2 Test pulse width 60 s 340 s Test pulse distance 5 ms 60 ms OSSD restart delay time 100 ms Tab 13 4 Status signals and control signals Signal Input Output Values Reset Input 24 V 15 mA...

Page 43: ...sioned drawings 60 225 36 4 5 106 75 4 3 16 3 38 3 all dimensions in mm Fig 13 1 Dimensioned drawing of MSI MD FB muting controller 13 3 Dimensioned drawings Accessories Mounting plate BT MSI MD_FB al...

Page 44: ...Technical data Leuze electronic MSI MD FBX 44 Mounting bracket BT MSI MD_FB L all dimensions in mm Fig 13 3 Mounting bracket BT MSI MD_FB L...

Page 45: ...5 m connection cable with angled socket 678071 CB M12 10000E 8WF 10 m connection cable with angled socket 678072 CB M12 15000E 8WF 15 m connection cable with angled socket 678073 CB M12 25000E 8WF 25...

Page 46: ...plate for mounting muting controller MSI MD FB on side or rear on UDC DC columns or for wall mounting 427303 BT MSI MD FB L Mounting bracket for interior mounting of muting controller MSI MD FB in UD...

Page 47: ...EC Declaration of Conformity Leuze electronic MSI MD FBX 47 15 EC Declaration of Conformity...

Reviews: