Mounting
Leuze electronic
MSI-MD-FBX
20
6.1.2
Mounting on the UDC device column
Mount the muting controller on the side or on the rear of the UDC device column of the receiver of the
safety sensor. The required mounting plate is available as an accessory (see chapter 14 "Order guide and
accessories").
1
2
3
1
Mounting plate BT-MSI-MD-FB
2
Muting controller
3
UDC device column
Fig. 6.2:
Mounting on side/rear on the UDC device column
6.1.3
Mounting on the system
Mount the muting controller on the system via three mounting eyes for M4 screws.
6.2
Arrangement of the muting sensors
Muting sensors detect material and supply the signals necessary for muting. Standard IEC/TS 62046 pro-
vides basic information on arranging the muting sensors. This information must be observed when mount-
ing the muting sensors.
WARNING
Improper installation may result in serious injury!
If the distance between transmitter and receiver is larger than the width of the object so that
gaps of more than 180 mm are created, suitable measures, e.g. through additional guarding,
must be taken to stop the dangerous movement before persons enter the area.
Ä
Make sure that no persons can reach the danger zone alongside the transport material dur-
ing muting.
Ä
Make sure that muting is only temporarily activated and only as long as the access to the
danger zone is blocked by the transport material.
NOTICE
If accessible distances exist between the transport material and the safety sensor, PS mats or
wicket gates monitored with safety switches have been tried, tested and proven as additional
safeguards. Such measures prevent injuries caused, for example, by crushing in the access
area.