Electrical connection
Leuze electronic
MLC 510 AS-i Host/Guest
33
7
Electrical connection
WARNING
Faulty electrical connection or improper function selection may result in serious injury!
Ä
Only allow competent persons to perform the electrical connection.
Ä
Make certain that the safety sensor is protected against overcurrent.
Ä
For access guarding, activate the start/restart interlock and make certain that it cannot be
unlocked from within the danger zone.
Ä
Ä
Select the safety-relevant functions for the safety sensor (see chapter 4 "Functions").
NOTICE
Laying cables!
Ä
Lay all connection cables and signal lines within the electrical installation space or perma-
nently in cable ducts.
Ä
Lay the cables and lines so that they are protected against external damages.
Ä
For further information: see EN ISO 13849-2, Table D.4.
7.1
Pin assignment transmitter and receiver
7.1.1
MLC 500/A transmitter
MLC 500/A transmitters are equipped with a 5-pin M12 connector.
2
3
1
4
5
FE
Fig. 7.1:
Pin assignment transmitter
Tab. 7.1:
Pin assignment transmitter
Pin
Transmitter
1
AS-i +
2
n.c.
3
AS-i -
4
n.c.
5
n.c.