Technical data
Leuze electronic
MC3x
49
Table 13.11:
Connection
Table 13.12:
Environment
Table 13.13:
Housing
Output contacts, OSSDs
OSSD protective circuit
2 normal open contacts (N/O), 1 normal closed contact
(N/C)
Provide suitable spark extinction (via relays, contac
-
tors)
OSSD switching capacity in accordance with
EN 60947-5-1
AC-15 (Ue / Ie):
DC -13 (Ue / Ie):
240 V / 0.9 / 3.5
×
10
5
24 V / 1.5 A / 1
×
10
5
Auxiliary contacts, switching capacity, max.
24 V DC, 1.5 A
Internal safeguarding of U
b
750 mA per PTC Multifuse
External contact fuse protection in accordance
with EN 60269-1
4 A gG
Protection rating acc. to EN 60529
Housing IP 40, terminals IP 20 for installation in cabinet
or housing with protection rating of at least IP 54
required
Finger-safe acc. to DIN VDE 0106 part 100, maximum
stripped length of the connection cables 8 mm
Connection cross-section (GS-ET-20:2009)
1 x 0.2 to 2.5 mm
2
, fine-wired or
1 x 0.25 to 2.5 mm
2
, fine-wired with wire-end sleeves
2 x 0.5 to 1.5 mm
2
, fine-wired with Twin wire-end
sleeves
1 x 0.2 to 2.5 mm
2
, single-wired or
2 x 0.25 to 1.0 mm
2
, fine-wired with wire-end sleeves
2 x 0.2 to 1.5 mm
2
, fine-wired
2 x 0.2 to 1.0 mm
2
, single-wired
Ambient temperature, operation
Relative humidity (non- condensing)
0 … +55 °C
4 … 100 %
Ambient temperature storage
Relative humidity (non- condensing)
-25 … +70 °C
5 … 95 %
Vibration resistance
EN 60947-5-3:2005
Dirt level, external,
in accordance with EN 60947-1
2
EMC compliance
EN 60947-5-3:2005
EN 61000-6-3:2007
EN 61000-6-2:2005
EN 55011:2003
Material
Plastic (PA)
Dimensions (dimensional drawings)
see chapter 14 „Dimensions and weights“
Installation point
Arbitrary, on 35 mm DIN top-hat supporting rail in
accordance with DIN EN 50022
Weight
see table 14.1
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: [email protected]