Configuration steps for a Rockwell control without EDS support
10.4.1
Integrating the hardware into the PLC using the generic Ethernet module
In configuration tool
RSLogix 5000 up to software version 20.00
, a so-called
generic
Ethernet module
is created under the Communication path for the BCL 558
i
.
Figure 10.3: Generic Ethernet module
The input mask for the generic module describes the following parameters to be set:
• The name of the participant (can be selected freely; e.g. BCL 558
i
).
• The format of I/O data (data - SINT = 8 bits).
• The IP address of the participant.
• The address and length of the input assembly (instance 100, instance 101 or instance
102; min 1 byte - up to max. 266 bytes for the default input assembly of the read
results).
• The address and length of the output assembly (instance 120, instance 121 or
instance 122; min 1 byte - up to max. 263 bytes for the default output assembly).
• The address and length of the configuration assembly (instance 190; 3 bytes).