23
INSTALLATION AND MAINTENANCE
VARMECA - 10
Variable speed motor or geared motor
GENERAL INFORMATION
LEROY-SOMER
Réf. 3195 - 4.33/d - 12.99
1.3.2 - Specifications and functions
SPECIFICATIONS
VARMECA - 10
Overload
150 % of In for 40s, 10 times per hour
Motor frequency variation range
- from 12 to 80Hz at constant torque *
- from 12 to 50 Hz for general applications *
- from 6 to 220 Hz - range adjustable using parameter-setting option **
(see VARMECA - 10 manual - parameter-setting)
Efficiency
97.5 % x motor efficiency
CONTROL
VARMECA - 10
Speed reference
- Analogue reference
(0V or 4mA = minimum speed)
(10V or 20mA = maximum speed)
- 0 - 10V with integrated potentiometer
- 0 - 10V with remote potentiometer option *
- 0 - 10V with external reference *
- 4 - 20mA with external reference *
- reference with internal potentiometer (CVI - VMA option)
- limitation of maximum speed with internal potentiometer (CVI - VMA option)
• Digital reference
- 1 to 3 preset speeds (accessible with the parameter-setting option **)
Speed regulation
Regulation of a reference with the integrated PI loop (accessible with the parameter-
setting option **)
Specifications of the PI sensor : 0 - 10V signal
Run/Stop
• With 3-phase power supply (10 times per hour max)
• With remote volt-free contact
• With integrated Run/Stop control (CMA option)
Forward/Reverse
• With internal connection on the terminal block
• With remote volt-free contact
• With integrated Forward/Reverse/Stop control (CMA VAR option)
Stop mode
• On ramp (with volt-free contact or integrated Run/Stop control)
• Freewheel stop (by cutting the 3-phase power supply)
• Freewheel stop (with volt-free contact or integrated Run/Stop control)
(accessible with parameter-setting option **)
• On electromechanical brake (integrated control)
Ramps
• Selection of acceleration and deceleration ramps with volt-free contact : 2s or 5s
(factory setting 5s for F max 80 Hz)
• Ramps adjustable from 0 to 20s (accessible with the parameter-setting option **)
INDICATIONS
VARMECA - 10
Display
Indicator lamp
• Permanent green light : mains connected
• Flashing green light : current limit
• Permanent or flashing orange light : overload
• Flashing red light : fault, under- or overvoltage
• Permanent red light : other fault
Relay
• Speed controller fault
volt-free contact - 1A - 250V - contact open, speed controller faulty or powered
down
Analogue output
• Speed image 0 - 10V, 3mA
• 0V = zero speed
• 10V = maximum speed
* Adjust using mini DIP switch (see section 2.3)
** See VARMECA - 10 manual - Parameter-setting.
en