LEROY-SOMER
4946 - 2013.07 / a
POWERDRIVE MD2CS
37
en
InstallatIon and maIntenance
Chassis-mounted variable speed drive
PaRameteR-settInG InteRFace and oPtIons
5.2.4.3 - MDX-Speed feedback option combined with a
CM-Fieldbus module
note: In the case of the use of one of these modules with
mdX-I / o tImeR module refer directly to §.5.2.4.4
In this case, 2 devices are needed:
+
mdX-encodeR
or
mdX-ResolVeR
MDX Speed
feedback option
CM Fieldbus module
cm-modBUs,
cm-can-oPen or
cm-PRoFIBUs
or
cm-etHeRnet or
cm-etHeRnet-IP
• on the mdX-speed feedback option: remove the plastic
knock-out (4)
• Insert the back of the cm-Fieldbus housing into the space
freed up (5) and screw tight (6) (4x torx 8 screws)
•
The CM module must be inserted carefully to avoid
damaging the connector.
4
5
6
6
•
Install the MDX-Speed feedback with the fieldbus module
on the
POWERDRIVE MD2CS
, as shown in section 5.2.4.2.
5.2.4.2 - MDX-Speed feedback or MDX-Fieldbus option
note: In the case of the use of one of these modules with
mdX-I / o tImeR module refer directly to §.5.2.4.4
• Remove the black plastic protective cover from the drive
control board (connector protection) (1).
• align the option over the drive connector (2). the option
connector is located on the underside of the housing. Press
gently until it clicks into place.
• screw the option onto the control board with the supplied
screws (3). do not exceed a maximum tightening torque of
2 n.m.
3
1
2
OR
Fieldbus module
speed feedback
module