background image

- 7 -

 

4.2.3  Set NO LOAD SHUTDOWN switch (special optional) to ON position to shutdown UPS  

 

 

automatically when power fails and all connected loads are less than 60 W in order to  

 

 

save battery power.  (This optional switch is set at OFF position as default from factory)

 

 

If the connected load is PABX which consumes power less than 60 Watt, set the switch 

 

 

to OFF position.

 

 

Note: 

For the standard product which does not have the NO LOAD SHUTDOWN 

 

 

 

 

switch at the rear side of the UPS, UPS has built-in this features. It will auto-   

 

 

 

 

matically shutdown when power fails and detects that connected loads are   

 

 

 

 

less than 60 Watt.

 

4.2.4  Plug in the electrical appliances such as computer, monitor, modem, fax machine, etc.  

 

 

to the UPS OUTPUT outlets at the rear side of the UPS.

 

4.2.5  Plug in the laser printer to the “FOR LASER PRINTER” outlet which is connected to surge 

 

 

protection system. (This socket does not supply backup power when power fails)

 

4.2.6  Plug in the AC INPUT power cord to the utility line.

 

4.2.7  Turn on the POWER switch of the UPS and then turn on all connected loads.

 

4.2.8  Test the UPS after the battery is charged by turn on POWER switch and wait until the  

 

 

LINE indicator is lit. Then, turn on all connected loads. To simulate blackout situation,  

 

 

unplug AC INPUT power cord from utility line, UPS will supply backup power to loads  

 

 

automatically.  The ALARM indicator blinks slowly and alarm sounds simultaneously.

 

 

Then, plug the AC INPUT power cord back to utility line. The ALARM indicator is off,  

 

 

no alarm sound and the LINE indicator is lit. Notice that all connected loads are still    

 

 

operating during test. For more confidence, repeat the test for 3-4 times.

 

4.2.9  After finished work with the computer, shut it down and turn off the UPS to keep 

 

 

sufficient battery power is available when there is blackout.

 

4.2.10  If you have to storage UPS for long period of time, be sure that battery is fully charged 

 

 

and it need to be recharged every three months to preserve the condition of the 

 

 

internal battery. Only connect the UPS to utility line and turn on, then leave the UPS   

 

 

connected to utility line for at least 8 hours.

- 8 -

TROUBLESHOOTING

Symptoms

Possible causes

Solutions

Turn on POWER switch, LINE 
indicator extinguished and 
alarm sounds, but UPS oper-
ates normally.

AC INPUT power cord is not 
properly plugged in to the 
utility line.

Properly plug in the AC INPUT power 
cord.

There is no power supply to 
AC input power cord.

Move the UPS to another wall outlet. 
If the problem persists, please con-
tact us.

Magnetic breaker is  tripped.

Reset breaker at the rear side of the 
UPS.

ALARM indicator blinks and 
alarm sounds simultaneously. 
Magnetic breaker does not 
trip.

AC input power cord is not 
properly plugged in to the 
utility line.

Properly plug in the AC INPUT power 
cord.

Main circuit breaker of
AC power source is tripped.

Reduce loads which are connected 
to the same wall outlet or move the 
UPS to another wall outlet.

ALARM indicator is lit and 
alarm sound continuously. 

 

UPS does not supply backup 
power and magnetic breaker  
tripped.

UPS is overloaded or short 
circuit.

1. Turn off the UPS and reduce some 
loads until the total consumption of 
all connected loads are less than UPS 
power rating.
2. Reset breaker at the rear side of 
the UPS.

When a blackout occur, the 
ALARM indicator is lit and 
alarm sound continuously. 
Magnetic breaker  is normal, 
but UPS does not supply 
backup power.

UPS is overloaded.

Turn off the UPS and reduce some 
loads until the total consumption of 
all connected loads are less than UPS 
power rating.

When a blackout occur, the 
LINE and ALARM indicators 
extinquished and no alarm 
sound.  UPS does not supply 
backup power.

Battery power is running out.

Once the utility line turns back to 
normal, turn on the UPS for at least 8 
hours to recharge its battery.

UPS supplies backup power 
very short time.

UPS is overloadded.

Reduce some loads until the total 
power consumption of all connected 
loads are less than UPS power rating.

Battery is deteriorating.

Turn on the UPS for at least 8 hours 
to recharge its battery, then test. if 
the symptom persists, it need to re-
place the new battery. Please con-
tact us.

Summary of Contents for VIPER

Page 1: ...on 1 1 3 Battery safety 2 2 INTRODUCTION 3 2 1 General 3 2 2 Features 3 2 3 Optional 3 2 4 Special Optional 4 3 FRONT AND REAR PANEL 4 3 1 Front panel 4 3 2 Rear panel 5 4 INSTALLATION AND OPERATION 6 4 1 Preparation 6 4 2 Installation 6 5 TROUBLESHOOTING 8 6 BATTERY REPLACEMENT 9 7 STORAGE 10 8 SOFTWARE INSTALLATION 10 ...

Page 2: ...nstructions and caution markings on the UPS and all connected loads and all sections of this user guide 1 2 2 Install this unit in a temperature and humidity controlled indoor area with adequate air flow and away from chemical particles or flammable substances Avoid installing the unit near radio transmission station heat dissipation equipment and direct sunlight 1 2 3 This unit has ventilation gr...

Page 3: ...the laser printer from surges This outlet does not supply backup power when power fails Automatic No load shutdown UPS shuts down itself automatically when there is no connected load when power fails in order to save battery power Automatic restart After the utility line turns back to normal UPS will restart itself automatically Automatic UPS and Battery Test When startup the UPS it will start tes...

Page 4: ...own when power fails and there is no connected loads Total power of all connected loads are lower than 60 Watt This special optional switch is not supplied with the standard product 6 3 2 9 Additional UPS Output option The special optional extra Europe CEE 7 socket which is connected to UPS backup power system These special optional socket is not supplied with standard product INSTALLATION AND OPE...

Page 5: ...e condition of the internal battery Only connect the UPS to utility line and turn on then leave the UPS connected to utility line for at least 8 hours 8 TROUBLESHOOTING Symptoms Possible causes Solutions Turn on POWER switch LINE indicator extinguished and alarm sounds but UPS oper ates normally AC INPUT power cord is not properly plugged in to the utility line Properly plug in the AC INPUT power ...

Page 6: ...storage UPS for long period of time be sure that battery is fully charged and it need to be recharged every three months to preserve the condition of the internal battery 7 1 Plug the AC INPUT power cord to utility line 7 2 Turn on the POWER switch and leave the UPS connected to the utility line for at least 8 hours 7 3 Test the UPS by following the section 4 2 8 7 4 Turn off the UPS and disconnec...

Page 7: ...ely installed Open the Easy Mon X Setup Then click Auto Detect UPS button to search for UPS and communication port automatically 8 8 Once the location of UPS communication port has been found Open the Easy Mon X Spy program to monitor power data and operating status of the UPS LEN MAN UPS 107 Rev 3 00 2012 www leonics com Copyright 2012 Leonics Co Ltd All rights reserved ...

Reviews: