background image

 

 
 

LMS

BMS

 

Operating

 

Manual

 

Page

 

13

 

 

 

DC POWERED SOLENOID CONTROL 

HARDWARE SUPPLIED BY OTHERS 

 

Description:

 

This solution is for systems that utilize a DC powered solenoid valve and want to make use of the SPDT relay 
switch included with LMS-188-4P-BMS. 

Solenoid valve and associated power supply are to be provided by 

others.

 

 

Application:

 

The primary application is in systems where it is desirable to control a DC powered solenoid in the event that 
the alarm on the LMS-188-4P-BMS is active. When in non-alarm condition the relay is in a N.O. state and the 
solenoid will allow water to flow through it freely. Once the alarm is active, the relay on the LMS-188-4P-BMS 
will switch to N.C. and the solenoid will shut down. 

Solenoid valve and associated power supply are to be 

provided by others.

 

 

Installation:

 

Solenoid power supply is to be supplied by others and is not available from Leonard Valve. The relay contacts 
are rated up to 30 V/1A. See wiring diagram below for reference. Do Not Energize LMS-188-4P-BMS or 
solenoid valve until wiring is complete. 

Solenoid valve and associated power supply are to be provided by 

others.

 

 

1.

 

Connect positive side of power supply to the 

COMMON

 terminal (

2

). 

2.

 

Connect either terminal 

1 or 3

 from LMS-188-4P-BMS relay switch to positive side 

of DC solenoid. Use terminal 

1

 with N.C. solenoids; use terminal 

3

 with N.O. solenoids. 

3.

 

Connect neutral side of power supply directly to neutral side of DC solenoid.  

 
 
 

Summary of Contents for LMS-188-4P-BMS

Page 1: ...Avenue Cranston RI 02910 Tel 401 461 1200 Fax 401 941 5310 Toll free 800 222 1208 www leonardvalve com G LMS 188 4P BMS August 2018 WARNING This product can expose you to chemicals including lead whi...

Page 2: ...4 Temperature Alarms 4 Low High Alarm Limits 4 Min Max Actual Readings 4 Installation Instructions 5 Setting the IP Address 5 LMS BMS ProtoNode Connectivity Wiring Diagrams 6 LMS Overview 8 RDU Option...

Page 3: ...nt button MUTE MENU Sensor Probe The probes supplied with the Multi Probe Alarm System are highly accurate temperature sensors The sensor may be put in water or other mild aqueous solutions from 148 F...

Page 4: ...up Shows LMS 188 4P BMS startup screen NO BATTERY Power Down Install Battery The unit will run without a backup battery but will show NoBatt on the display to indicate lack of backup battery When a ba...

Page 5: ...l wait the Relay Delay time before tripping the Relay Limit Parameters 1 Low 1 High 2 Low 2 High 3 Low 3 High 4 Low 4 High Time Parameters 1AlarmDelay 2AlarmDelay 3AlarmDelay 4AlarmDelay RelayDelay Mu...

Page 6: ...ne 2 Define 3 Define 4 Define 0 tenthC 1 wholeC 2 tenthF 3 wholeF 4 wholeRH Relay Def 0 single unit relay 1 individual channel relays DoorAlarm 1 AlarmOnContactClosed 0 NoAlarm 1 AlarmOnContactOpen To...

Page 7: ...n the same Ethernet Subnet as the BMS See Figure 1 FIGURE 1 If Building Management System DOES NOT USE Ethernet IP Protocol In this case the LMS 188 4P BMS Ethernet port can be directly connected to t...

Page 8: ...LMS BMS Operating Manual Page 7...

Page 9: ...mes 1AlarmDelay 2AlarmDelay 3AlarmDelay 4AlarmDelay RelayDelay Mute Special Group SETUP LMS IP1 LMS IP2 LMS IP3 LMS IP4 LMS IP 1 2 3 4 ProtoNode1 ProtoNode2 ProtoNode3 ProtoNode4 ProtoNode IP 1 2 3 4...

Page 10: ...ESET 1 ActualMin 144 F ActualMax 152 F 2 ActualMin 52 F ActualMax 59 F 3 ActualMin 118 F ActualMax 124 F 4 ActualMin 107 F ActualMax 118 F Min Max Reset RESET to confirm STEP to cancel Relay Test At R...

Page 11: ...h in the N O Normally Open position this will be correct for the majority of installations however if your alarm device opens its contacts when it alarms simply slide the switch to the N C position 3...

Page 12: ...t the output contacts to their normal non alarm state if the alarm condition persists the yellow LED will again flash to indicate timing and after timing out will light the red LED and change the outp...

Page 13: ...quires a dedicated 110 VAC outlet to plug into See wiring diagram below for reference Do Not Energize SCO LMS 188 4P BMS or solenoid valve until wiring is complete Solenoid valve and associated power...

Page 14: ...arm is active the relay on the LMS 188 4P BMS will switch to N C and the solenoid will shut down Solenoid valve and associated power supply are to be provided by others Installation Solenoid power sup...

Page 15: ...LMS BMS Operating Manual Page 14...

Reviews: