10
Parameter reference
10.2
Parameters of the communication module for slot MXI1
76
Lenze · E94AYCEC Communication module (POWERLINK CN) · Communication Manual · DMS 3.0 EN · 08/2014 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C13126
C13127
C13131
Parameter | Name:
C13126 | EPL CN: Frame collisions
Data type: UNSIGNED_32
Index: 11449 = 0x2CB9
EPL index: See subcodes
The code indicates the number of POWERLINK collisions detected by the controlled node.
Each event is counted. Every single event is followed by an error message. No threshold value management is
implemented.
Setting range
(min. value | unit | max. value)
0
4294967295
Subcodes
Lenze setting
Info
EPL index
C13126/1
0
CumulativeCnt_U32
0x1C0A.0x01
Read access
Write access
CINH
PLC-STOP
No transfer
PDO_MAP_RX
PDO_MAP_TX
COM
MOT
Parameter | Name:
C13127 | EPL CN: Sync loss
Data type: UNSIGNED_32
Index: 11448 = 0x2CB8
EPL index: See subcodes
The controlled node expects SoC frames in time intervals which correspond to the cycle time (
The code indicates the error counters for missing SoC frames.
The monitoring response is determined via
Setting range
(min. value | unit | max. value)
0
4294967295
Subcodes
Lenze setting
Info
EPL index
C13127/1
0
CumulativeCnt_U32
0x1C0B.0x01
C13127/2
0
ThresholdCnt_U32
0x1C0B.0x02
C13127/3
9
Threshold_U32
0x1C0B.0x03
Read access
Write access
CINH
PLC-STOP
No transfer
PDO_MAP_RX
PDO_MAP_TX
COM
MOT
Parameter | Name:
C13131 | EPL CN: Frame error (CRC)
Data type: UNSIGNED_32
Index: 11444 = 0x2CB4
EPL index: See subcodes
The code indicates the number of frame checksum errors detected by the controlled nodes.
The monitoring response is determined via
Setting range
(min. value | unit | max. value)
0
4294967295
Subcodes
Lenze setting
Info
EPL index
C13131/1
0
CumulativeCnt_U32
0x1C0F.0x01
C13131/2
0
ThresholdCnt_U32
0x1C0F.0x02
C13131/3
9
Threshold_U32
0x1C0F.0x03
Read access
Write access
CINH
PLC-STOP
No transfer
PDO_MAP_RX
PDO_MAP_TX
COM
MOT