Technical data
General data and operating conditions
4
42
EDK94AZRP45 DE/EN/FR/ES/IT 5.0
4
Technical data
4.1
General data and operating conditions
Conformity and approval
Approval
UR
UL508
Industrial Control Equipment, Underwriter
Laboratories (File-No. E219022) for USA and Canada
Mains data
Mains types
With grounded neutral (TT/TN systems)
Operation permitted without restrictions
IT systems
Max. mains voltage 400 V!
Observe instructions for special measures in the
documentation for the basic device!
Protection of persons and equipment
Enclosure
EN 60529
IP20
Not in the wire range of the
terminals
NEMA 250
Protection against
contact to type 1
Earth leakage current
IEC/EN 61800-5-1 > 3.5 mA AC
> 10 mA DC
Observe regulations and
safety instructions!
Insulation resistance
IEC/EN 61800-5-1 < 2000 m site altitude: overvoltage category III
> 2000 m site altitude: overvoltage category II