ENGLISH
16
Commissioning
Code
Possible Settings
IMPORTANT
No.
Name
Lenze Selection
1
Auto-TRIP reset delay
0.0
0.0
{s}
60.0 See c70
Operating time
counter
Display
Total time in status “Start”
0...999 h: format xxx
1000...9999 h: format x.xx (x1000)
10000...99999 h: format xx.x (x1000)
Mains connection
time counter
Display
Total time of mains = on
1
PI setpoint
0.0
c86
c87
2
S-ramp integration
time
0.0
0.0
{s}
50.0 • c82 = 0.0: Linear accel/decel ramp
• c82 > 0.0: Adjusts S-ramp curve for
smoother ramp
Minimum feedback
0.0
0.0
999
• Select feedback signal at C34
• If feedback is reverse-acting, set
c86>c87
7
Maximum feedback
100
0.0
999
PI setpoint accel/
decel
5.0
0.0
{s}
999
Sets rate of change for PI setpoint
PI mode
0
0 PI disabled
1 PI enabled: normal-acting
When feedback (terminal 8) exceeds
setpoint, speed decreases
2 PI enabled: reverse-acting
When feedback (terminal 8) exceeds
setpoint, speed increases
Feedback minimum
alarm
0.0
0.0
999
See C08, selections 9 and 10
7
Feedback maximum
alarm
0.0
0.0
999