Mechanical installation
Important notes
4
EDK82ZZ113 DE/EN/FR 2.1
25
H1_MechINS-Montageschritte-Var_E82ZZ
4
Mechanical installation
Important notes
ƒ The mounting location must always fulfill the operating conditions specified in the
Technical data. (
21). If necessary, take additional measures.
ƒ The mounting plate of the control cabinet must be:
– electrically conductive
– free of lacquer
ƒ The mechanical connections must always be ensured.
ƒ When E82ZZ75232B2x0 or E82ZZ11334B2x0 RFI filters are used together with mains
chokes ELN3-0088H035/ELN3-0150H024, keep a distance of at least 220 mm
between RFI filter and mains choke.
ƒ Basic devices of type E82
E
V... (built-in units) can be mounted onto the filter (standard
mounting) or to the right of the filter (mounting variant).
Basic devices of types E82
D
V... (push-through technique) and E82
C
V... (cold plate) can
only be mounted to the right of the filter (mounting variant).