Technical data
General data and operating conditions
3
EDK82ZZ113 DE/EN/FR 2.1
21
H1_Daten-TD_Montagebed_E82ZZ
3
Technical data
General data and operating conditions
Standards
Approval
UL
UL 508C, Component Power Conversion Equipment -
Accessories (file no. E132659) for the US and Canada
Mains data
Mains types
With grounded neutral (TT /TN systems)
Operation permitted without restrictions
IT systems
230 V
Observe instructions for special measures in the
documentation for the basic device!
400 V
Max. mains voltage 400 V!
Observe instructions for special measures in the
documentation for the basic device!
Protection
Type of protection
EN 60529
IP 20
Not in the wire range of
the terminals
NEMA 250
Protection against contact to
type 1
Insulation resistance
EN 61800-5-1
Overvoltage category III
> 2000 m: Overvoltage category II
Leakage current
EN 61800-5-1
E82ZZ...B200
E82ZZ...B210
> 3.5 mA
Observe regulations and
safety instructions!
E82ZZ...B220
< 3.5 mA
Ambient conditions
Temperature
Storage
-25 ... +60 °C
Transport
-25 ... +70 °C
Operation
-10 ... +55 °C
Current derating from +40 to +55 °C: 2.5 %/°C
Site altitude
0 ... 4000 m amsl
1000 ... 4000 m amsl: Current derating by 5 %/1000 m
Pollution
EN 61800-5-1
Pollution degree 2
Vibration resistance
EN 50178, IEC 61800-5-1,
Germanischer Lloyd,
general conditions
Acceleration-resistant up to 0.7 g
Mounting conditions
Mounting location
In the control cabinet
Position
Standard: between mounting plate and basic device
Variant: to the left of the basic device
Mounting position
Vertical, connections on top