Lenze 93 V004 Series Installation & Commissioning Download Page 15

Installation

3.3

Circuit for

Safe standstill with safety-oriented PLC

The example shows minimum wiring of the components. This ensures the troublefree operation of
the

Safe standstill

function of 93XX controllers.

S 1

S 2

+   2 4   V

K 4

O F F

O N

K 4

Y 1

S

af

et

y-

or

ie

nt

ed

 P

LC

0   V

F 1 . . F 3

L 2

L 1
L 3

In

pu

ts

O

ut

pu

ts

O

ut

pu

ts

In

pu

ts

O

ut

pu

ts

M o t o r   b r a k e

S t a r t - S t o p

m o m e n t a r y   c o n t a c t

p u s h b u t t o n

S 3

E m e r g e n c y

o f f

E m e r g e n c y   o f f

S 4

S a f e t y   d o o r

m o n i t o r i n g

M a i n s   c o n t a c t o r

C

lo

ck

pu

ls

ou

tp

ut

s

Q S P

R F R

9 3 x x

X 1 1

G N D

I G B T

A 3

V 0 0 4

    D C  

+ 2 4   V

C W

r o t a t i o n

C C W

r o t a t i o n

K

S R

K 3 2

3 4

3 3

E 1

K 3 1

E 2

2 8

3 9

5 9

X 5

A 1

n = 0

A 4

Fig. 5

Minimum wiring for 93XX-V004 controllers with safety-oriented PLC
to EN 954-1 control category 3 and EN 1037, stop category 1 to EN 60204-1

3.3.1

Description

For a circuit with safety-oriented PLC control follow EN 954-1 control category 3 and EN 1037. The
circuit in Fig. 5 shows a stop category 1 stop function according to EN 60204-1 (with safety door
monitoring).

The circuit is positively dynamic for the emergency off function (S3), door locking (S4) and
feedback contact of the safety relay (K

SR

), i. e. proper and correct functioning of the external

circuit of the PLC and PLC inputs can be ensured through a clock signal.
The circuits for emergency off and door lock are two channel circuits protected against short
circuits between signal cables.

The integrated switching devices are equipped with positively driven contacts.

The PLC outputs for motor brake (Y1) and mains contactors (K4) are two-channel circuits.
The safe activation of the functions is ensured by the second switch-off circuit in the output
module of the PLC. Additionally, the PLC reads the NC contact of K4.

Note for the PLC programmer!

In the event of faulty operation of the safety relay for the external pulse inhibit, the power supply for
the controller must be switched off via the mains contactor (K4) (2nd switch-off circuit).

The wiring instructions shown in Fig. 1 must be considered accordingly!

Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: [email protected]

Show/Hide Bookmarks

Summary of Contents for 93 V004 Series

Page 1: ...Installation Commissioning EDB9300EN V004 N Global Drive 9300 series Variant V004 Safe standstill N Buy www ValinOnline com Phone 844 385 3099 Email CustomerService valin com Show Hide Bookmarks...

Page 2: ...Explanation E 2002 Lenze Drive Systems GmbH No part of this documentation may be reproduced or made accessible to third parties without written consent by Lenze Drive Systems GmbH All indications giv...

Page 3: ...solution offers the following advantages no external motor contactor reduced wiring expenses saves space improved EMC the motor cable screen must not be interrupted 1 2 About these Instructions These...

Page 4: ...drive controllers in machines commissioning i e starting of operation as directed is prohibited until it is proven that the machine complies with the regulations of the EC Directive 98 37 EC Machiner...

Page 5: ...in the Instructions After the controller has been disconnected from the supply voltage live components and power connection must not betouched immediately sincecapacitors could becharged Please obser...

Page 6: ...ng the Safe standstill function additional measures are required for Emergency off Motor and controller are not isolated and not equipped with a service switch or repair switch An Emergency off requir...

Page 7: ...5 A 60 V DC max 0 5 A 200 V DC 3 4 3 3 K 3 2 K 3 1 3 4 3 3 K 3 2 K 3 1 Control voltage contact coil Control voltage contact contact AC 1500 Vrms for 1 min AC 1500 Vrms for 1 min Wiring of plug X11 El...

Page 8: ...1 1 Description For a circuit with a safety relay for emergency off and door lock follow EN 954 1 control category 3 and EN 1037 The circuit in Fig 1 shows a stop function of stop category 1 to EN 602...

Page 9: ...always be braked to a controlled standstill when running at max speed t3 to t4 t3 to t5 tQSP min 100 ms guide value Set the time relay K2a so that tQSP min 100 ms safety time will always be achieved T...

Page 10: ...essed the drive will be braked to a controlled standstill according to stop category 1 of EN 60204 1 The Quick Stop input QSP is set immediately at the controller by opening the NO contact of K3 t3 vi...

Page 11: ...f s w i t c h i n g d e v i c e S a f e t y d o o r s w i t c h i n g d e v i c e K 4 A 1 A 2 S t a n d a r d P L C O u t p u t s I n p u t s I n p u t s K 4 K 3 K 3 K 3 K 4 O u t p u t s K 4 t A 1 t...

Page 12: ...on for the drive The PLC control detects if the mains contactor K4 or the start stop relay K3 is not released when checking the configuration of the NC contact before restarting the machine If the PLC...

Page 13: ...ked to a controlled standstill when running at max speed t3 to t4 t3 to t5 tQSP min 100 ms standard value Set the time t3 to t5 so that tQSP min 100 ms ensures safety This ensures a controlled standst...

Page 14: ...top QSP is set immediately via terminals E1 and E2 of the controller The controller brakes with tQSP in a controlled mode until the motor has been stopped t4 If the controller sends the signal n 0 ter...

Page 15: ...954 1 control category 3 and EN 1037 The circuit in Fig 5 shows a stop category 1 stop function according to EN 60204 1 with safety door monitoring The circuit is positively dynamic for the emergency...

Page 16: ...at max speed t3 to t4 t3 to t5 tQSP min 100 ms standard value Set the time t3 to t5 so that tQSP min 100 ms ensures safety This ensures a controlled standstill according to stop category 1 of EN 60204...

Page 17: ...oors are open 3 3 5 Emergency off function If S3 EMERGENCYOFF is pressed the drive is braked to acontrolled standstillaccording to stop category 1 of EN 60204 1 A Quick Stop QSP is set immediately via...

Page 18: ...ctive must be assigned to digital output terminal Code C0118 1 selection 0 Excerpt from code table Code Possible settings IMPORTANT No Name Lenze Selection C0117 1 2 3 4 CFG DIGOUT CFG DIGOUT CFG DIGO...

Page 19: ...2 Hanging loads must be mechanically fastened blocked 3 Safety relay KSR Safe standstill function protection against unintended start must be controlled 4 Circuit breakers S4 open when the controller...

Page 20: ...quence B a s i c s e t t i n g P o w e r o n K S R d e f e c t i v e M o t o r s t a r t K S R a c t i v e M o t o r i s r o t a t i n g E r r o r e v a l u a t i o n 2 n d s w i t c h o f f c i r c u...

Page 21: ...bkJsMMQ bk QKM 5 1 2 Safe standstill with a standard PLC control Fig 9 PLC program Safe standstill with a standard PLC control Buy www ValinOnline com Phone 844 385 3099 Email CustomerService valin co...

Page 22: ...dge switch S2 ON 0005 Power ON contactor K4 E_S2_EIN E_S2_ON Input switch S2 on M_NegFlanke_Aus M_NegEdge_off Flag negative edge switch S1 off E_A1_NOT_AUS E_A1_EMERGENCY_OFF EMERGENCY OFF signalling...

Page 23: ...rotation Input preselection drive motor counter clockwise rotation E_Rechtslauf E_clockwise rotation Input preselection drive motor clockwise rotation E_A1_NOT_AUS E_A1_EMERGENCY_OFF EMERGENCY OFF si...

Page 24: ...oor A_NOT_AUS_K4 A_EMERGENCY_OFF_K4 BOOL Output fault K4 power disconnection 0017 Controller power supply off E_A1_NOT_AUS E_A1_EMERGENCY_OFF EMERGENCY OFF signalling contact switch unit A1 E_KSR_IMP_...

Page 25: ...ck Stop ramp set in the controller safety of 100 ms as standard value t3 after t5 T5_EMERGENCY_OFF_do or Monitors the control units for Emergency off circuit Safety door When the mains contactor is sw...

Page 26: ...re OR linked C0136 1 displays the control word C013 5 Quick Stop QSP Internal drive controller function for the operational stop Quick Stop The drive is braked to standstill via the deceleration ramp...

Page 27: ...ements of the machine Stop functions of category 0 1 must be operational in all operating modes A stop of category 0 must have priority Stop functions must have priority over assigned start functions...

Page 28: ...occurrence of errors in this part the technologies used 5 3 3 2 Notes for selection B C a t e g o r y 1 2 3 4 S t a r t i n g p o i n t f o r r i s k a s s e s s m e n t o f t h e s a f e t y r e l a...

Page 29: ...test function 3 6 2 4 The requirements of B must be fulfilled The official safety regulations have to be observed Safety related parts must be designed as follows in none of the parts a single error m...

Reviews: