RG-MHLON
20
LonWorks Network Variables
nciNmlSpeed
Definition
Network config input SNVT_rpm nciNmlSpeed
Explanation
This configuration property is used to provide the nominal speed of the motor.
Valid Range
1 to 65000 RPM
The value 0xFFFF represents invalid data.
Default Value 1800 RPM
nciNmlFreq
Definition
Network config input SNVT_freq_hz nciNmlFreq
Explanation
This configuration property is used to provide the nominal frequency of the motor.
Valid Range
0.0 - 650.00 Hz
Default Value 60.00 Hz
nciMinSpeed
Definition
Network config input SNVT_lev_percent nciMinSpeed
Explanation
This configuration property is used to define the minimum speed of a motor. Its
value is entered as a percentage of nominal speed, as defined by the Nominal
Speed (nciNmlSpeed) configuration value. The value of the minimum speed must
be validated against the value of the maximum speed as follows:
-163.840% <= minimum speed <= maximum speed <= 163.835%
Valid Range
-163.840% to 0.000 % or 0.000% to +163.835%
The value 0x7FFF represents invalid data.
Default Value 0.830%
nciMaxSpeed
Definition
Network config input SNVT_lev_percent nciMaxSpeed
Explanation
This configuration property is used to define the maximum speed of a motor. Its
value is entered as a percent of nominal speed, as defined by the Nominal Speed
(nciNmlSpeed) configuration value. The value of the maximum speed must be
validated against the value of the minimum speed as follows:
-163.840% <= minimum speed <= maximum speed <= 163.835%
Valid Range
-163.840% to 0.000 % or 0.000% to +163.835%
The value 0x7FFF represents invalid data.
Default Value 100.000%