![Lenze AC Tech LonWorks MCH Series Communications Manual Download Page 22](http://html.mh-extra.com/html/lenze-ac-tech/lonworks-mch-series/lonworks-mch-series_communications-manual_1882579022.webp)
19
RG-MHLON
LonWorks Network Variables
4.4 Supported Configuration Network Variables
NciSndHrtBt
Definition
Network config input SNVT_time_sec nciSndHrtBt
Explanation
This input configuration network variable provides the maximum send time for the
variable nvoDrvSpeed.
Valid Range
0.0 to 6553.5 sec
The value 0 disables the Send Heartbeat mechanism.
The value 0xFFFF represents invalid data.
Default Value 0 sec (disabled)
NciRcvHrtBt
Definition
Network config input SNVT_time_sec nciRcvHrtBt
Explanation
This configuration property is used to control the maximum time that elapses after
the last update to input network variables nviDrvSpeedStpt or nviDrvSpdScl. If
a timeout occurs, the module indicates an RX_FAIL condition to the drive which
induces the Serial Loss action described in Section 3.5.
Valid Range
0.0 to 6553.5 sec
The value 0xFFFF represents invalid data.
The value 0 disables the Receive Heartbeat mechanism.
Default Value 0 sec (disabled)
NciMinOutTm
Definition
Network config input SNVT_time_sec nciMinOutTm
Explanation
This input configuration network variable controls the minimum period of time that
expires before the network output variables can be propagated (resent).
Valid Range
0.0 to 6553.5 sec
The value 0xFFFF represents invalid data.
The value 0 disables transmission limiting.
Default Value 0.0 sec (disabled)