Troubleshooting: Cooling Sequence of Operation
COOLING SEQUENCE OF OPERATION
SIGNAL POLARITY REVERSED.
CONTROL WILL CONTINUE TO CALL FOR COOLING
IN THIS CONDITION.
STATUS ERROR CODE 5 + 4.
POWER ON
YES
IS POLARITY REVERSED?
THERMOSTAT CALLS FOR COOL.
COMPRESSOR AND CONDENSER FAN
ENERGIZED.
NO
IS THERE
PROPER GROUND?
YES
NO
INDOOR BLOWER ENERGIZED ON COOL SPEED
AFTER 2 SECOND DELAY.
DEMAND FOR COOL SATISFIED?
COMPRESSOR AND CONDENSER FAN DE-ENERGIZED.
INDOOR BLOWER DE-ENERGIZED AFTER 45-SECOND
DELAY.
YES
SIGNAL IMPROPER GROUND AT LED.
CONTROL WILL CONTINUE TO CALL FOR COOLING
IN THIS CONDITION.
STATUS ERROR CODE 5 + 4.