2. Install the PCIe expansion tray (see “Install the PCIe expansion tray” on page 151).
3. Install the chassis air baffle (see “Install the chassis air baffle” on page 66).
4. Install the top cover (see “Install the top cover” on page 148).
5. Reconnect the power cords and any cables that you removed.
6. If the server is installed in a rack, reinstall the server into the rack.
7. Power on the server and any peripheral devices.
Remove the front operator panel
Use this procedure to remove the front operator panel.
With the operator panel tray assembly removed from the system (see “Remove the operator panel tray
assembly” on page 92) , complete the following steps to remove the front operator panel:
Watch the procedure
. A video of the process is available:
• Youtube:
https://www.youtube.com/watch?v=pIb0bIyfkDY&=PLYV5R7hVcs-Ak9fT8QAx8fLbEivizjRtp
• Youku:
http://v.youku.com/v_show/id_XMzMyODU3NTY2NA==.html?spm=a2hzp.8253876.0.0&f=51276390
Step 1. Press on the two release tabs on the rear of the front operator panel, and carefully slide the
assembly out of from the tray assembly.
Figure 90. Front operator panel removal
If you are instructed to return the component or optional device, follow all packaging instructions, and use
any packaging materials for shipping that are supplied to you.
Install the front operator panel
Use this procedure to install the front operator panel.
Before installing the front operator panel:
1. Read the safety information and installation guidelines (see “Safety” on page iii and “Installation
2. Touch the static-protective package that contains the component to any unpainted metal surface on the
server; then, remove it from the package and place it on a static-protective surface.
To install the front operator panel, complete the following steps:
96
ThinkSystem SR860 Maintenance Manual
Summary of Contents for ThinkSystem SR860
Page 1: ...ThinkSystem SR860 Maintenance Manual Machine Type 7X69 7X70 ...
Page 8: ...vi ThinkSystem SR860 Maintenance Manual ...
Page 63: ...Figure 48 Server components Chapter 2 Server components 55 ...
Page 200: ...192 ThinkSystem SR860 Maintenance Manual ...
Page 210: ...202 ThinkSystem SR860 Maintenance Manual ...
Page 211: ......
Page 212: ...Part Number SP47A30805 Printed in China 1P P N SP47A30805 1PSP47A30805 ...