5 Connections
Analogue inputs E6
GEL 8251
21
5.9 Analogue
inputs
E6
1 2 3 4 5 6
The analogue inputs can be set for the measurement of
– currents 0 – 20 mA or
– voltages 0 – 10 V.
A jumper is provided for this purpose beside the terminal strip for each
of the max. 3 inputs.
Standard configuration: Current measurement (I)
For voltage measurement (U) fit the related jumper. For this pur-
pose the cover with the cable clips must be removed: Undo
4 knurled screws.
1 2 3 4
E6
AE1.1
AE1.2
AE1.3
I U
The measuring ranges are converted internally to a value range from 0…255 (1 byte).
/AE1.1...3
AE1.1...3
2/4/6
1/3/5
E6
Sensor
0 - 20 mA
/
0 - 10 V
Controller
45k
5k
50
0 - 20 mA
To stabilise the differential input it is recommended to connect the earth for the
external sensor supply to the analogue earth on the controller:
– terminal strip E5, terminals 1/3/5/7 or
– terminal strips A1–3, terminal 2