31
Installation and Maintenance
Service Manual
gas pipe
Liquid pipe
Liquid
valve
gas valve
Union nut
Pipe joint
3. Connect Indoor and Outdoor Pipes
(1) Remove the screw on the right handle and valve cover (only
for 18K unit) of outdoor unit and then remove the handle and
valve cover (only for 18K unit).(As show in Fig.20)
(2) Remove the screw cap of valve and aim the pipe joint at the
bellmouth of pipe.(As show in Fig.21)
(3) Pretightening the union nut with hand.
(4) Tighten the union nut with torque wrench .
Fig.21
(1) After tightening the screw, pull the power cord slightly to
check if it is firm.
(2) Never cut the power connection wire to prolong or shorten
the distance.
Note:
(2) Fix the power connection wire with wire clip.
Fig.22
handle
Note: the wiring board is for reference only,
please refer to the actual one.
Wire clip
Wiring board Grounding
wire
2
N
(1)
(1) Take sufficient protective measures when installing the
outdoor unit.
(2) Make sure the support can withstand at least four times the
unit weight.
(3) The outdoor unit should be installed at least 3cm above the
floor in order to install drain joint.(As show in Fig.18)
(4) For the unit with cooling capacity of 2300W~5000W, 6
expansion screws are needed; for the unit with cooling capacity
of 6000W~8000W, 8 expansion screws are needed; for the
unit with cooling capacity of 10000W~16000W, 10 expansion
screws are needed.
Note:
At least 3cm above the floor
8.6 Installation of Outdoor Unit
1. Fix the Support of Outdoor Unit(Select it according to
the actual installation situation)
(1) Select installation location according to the house structure.
(2) Fix the support of outdoor unit on the selected location with
expansion screws.
2. Fix Outdoor Unit
(1) Place the outdoor unit on the support.
(2) Fix the foot holes of outdoor unit with bolts.
(As show in Fig.19)
Fig.18
Foot holes
Foot holes
Fig.19
Fig.20
4. Connect Outdoor Electric Wire
(1) Remove the wire clip; connect the power connection wire
to the wiring terminal according to the color; fix the power
connection wire with screws.(As show in Fig.22)
Hex nut diameter(mm) Tightening torque(N m)
Φ6
15~20
Φ9.52
30~40
Φ12
45~55
Φ16
60~65
Φ19
70~75
Refer to the following table for wrench moment of force
:
.
U-shaped curve
Wall
Drain hose
The drain hos
can't raise
upwards
5. Neaten the Pipes
(1) The pipes should be placed along the wall, bent reasonably
and hidden possibly. Min. semidiameter of bending the pipe is
10cm.
(2) If the outdoor unit is higher than the wall hole, you must set
a U-shaped curve in the pipe before pipe goes into the room,
in order to prevent rain from getting into the room.(As show in
Fig.23)
Fig.23
Fig.24
(1) The through-wall height of drain hose shouldn't be higher
than the outlet pipe hole of indoor unit.(As show in Fig.24)
(2) Slant the drain hose slightly downwards. The drain hose
can't be curved, raised and fluctuant, etc.(As show in Fig.25)
Note:
Handle
Handle
Screw
Screw
Valve cover
N(1)
blue black
(brown)
yellow-
green
Indoor unit connection
LM009CO-100T432-1
LM012CO-100T432-1
LM018CO-100T432-1
Indoor unit connection
LM024CO-100T432-1
N(1)
2
blue black
yellow-
green
3
brown
Summary of Contents for Y6760
Page 20: ...17 Technical Information Service Manual AUTO COOL DRY FAN HEAT OFF...
Page 21: ...18 Technical Information Service Manual battery Cover of battery box remove reinstall...
Page 22: ...19 Technical Information Service Manual...
Page 51: ...48 Installation and Maintenance Service Manual LM024CI 100T432 1...
Page 70: ...67 Installation and Maintenance Service Manual...