Page 1

2019 Lennox Industries Inc.

Dallas, Texas, USA

THIS MANUAL MUST BE LEFT WITH THE

HOMEOWNER FOR FUTURE REFERENCE

General

This XP21 outdoor heat pump is designed for use with
HFC-410A refrigerant only. This unit must be installed with
an approved indoor air handler or coil. See the Lennox
XP21 Product Specifications bulletin (EHB) for approved
indoor component match ups.
These instructions are intended as a general guide and do
not supersede local codes in any way. Consult authorities
having jurisdiction before installation.

NOTICE !

For more in-depth information, consult the Installa­
tion and Service Procedures manual, available as
Corp.1031-L7 on LennoxPros.com or through the
Technical Support department at 800-453-6669.

INSTALLATION
INSTRUCTIONS

Dave Lennox Signature

®

Collection XP21 System

HEAT PUMPS
507217-02
8/2019

WARNING

Improper installation, adjustment, alteration, service or
maintenance can cause property damage, personal inju­
ry or loss of life.

Installation and service must be performed by a licensed
professional installer (or equivalent) or service agency.

CAUTION

Before attempting to perform any service or mainte­
nance, turn the electrical power to unit OFF at discon­
nect switch.

STEP 1 -- SETTING THE UNIT -- Clearances

CONTROL

PANEL ACCESS

LOCATION

6 (152)

36 (914)

12 (305)

30 (762)

24

(610)

LINE SET

CONNECTIONS

ACCESS PANEL

REAR VIEW OF UNIT

48 (1219)

MINIMUM CLEARANCE BETWEEN TWO UNITS

CLEARANCE ON ALL SIDES — INCHES (MILLIMETERS)

MINIMUM CLEARANCE

ABOVE UNIT

NOTES:

Clearance to access panel must be 30
inches (762mm).

Clearance to one of the other three
sides must be 36 inches (914mm).

Clearance to one of the remaining two
sides may be 12 inches (305mm) and
the final side may be 6 inches
(152mm).

NOTICE: 

Specific applications may require adjustment of the listed installation clearances to provide protection for the unit from

physical damage or to avoid conditions which limit operating efficiency. (Example: Clearances may have to be increased to
prevent snow or ice from falling on the top of the unit. Additional clearances may also be required to prevent air recirculation when
the unit is installed under a deck or in another tight space.)

FIGURE 1

Summary of Contents for XP21 Series

Page 1: ...nd service must be performed by a licensed professional installer or equivalent or service agency CAUTION Before attempting to perform any service or mainte nance turn the electrical power to unit OFF...

Page 2: ...18 1 2 470 8 203 1 25 4 7 16 113 LIQUID LINE INLET VAPOR LINE INLET ELECTRICAL INLETS BASE WITH ELONGATED LEGS SIDE VIEW ACCESS VIEW DISCHARGE AIR 37 940 024 THRU 036 47 1194 048 AND 060 16 7 8 429 8...

Page 3: ...nts from dryers water heaters and furnaces should be directed away from the outdoor unit Prolonged exposure to exhaust gases and the chemicals contained within them may cause condensation to form on t...

Page 4: ...ze barrier at least the same height and width as out door unit Install barrier 24 inches 610 mm from the sides of the unit in the direction of prevailing winds 24 610 WIND BARRIER PREVAILING WINTER WI...

Page 5: ...efore unit start up to pre vent compressor damage as a result of slugging CAUTION ELECTROSTATIC DISCHARGE ESD Precautions and Procedures Electrostatic discharge can affect electronic components Take c...

Page 6: ...wires between the thermostat and the furnace air handler con trol and four wires between the outdoor unit and the furnace air handler control When a thermostat cable with more than four wires is used...

Page 7: ...E TARGET 40 DEGREE TARGET DEFAULT 55 50 45 40 55 50 45 40 55 50 45 40 55 50 45 40 DEGREE TARGET 100 90 DEGREE TARGET 70 DEGREE TARGET 50 DEGREE TARGET 90F 70F 50F TARGET 90F 70F 50F 90F 70F 50F 100F 9...

Page 8: ...d up on the fan blade and orifice ring is when the outdoor ambient is below 35 F and the unit is OFF for more than 30 minutes PREVIOUS TERMINATION TEMPERATURE TERMINATION TEMPERATURE FOR NEXT DEFROST...

Page 9: ...t s o r f e d l l i w n o i t a n i m r e t g n i t t e s 1 J e h t w o l l o f m u m i x a M E T O N r o f d e w o l l a e m i t s e t u n i m 4 1 s i t s o r f e d See table on Page 10 Next defrost...

Page 10: ...eached the specified defrost termination temperature in less than 14 minutes Termination temperature set on outdoor control is 50 F 70 F 90 F or 100 F Defrost for 14 minute maximum without the coil te...

Page 11: ...isplay optional 2 R to L connection is required for this model when using the ComfortSense 7000 catalog number Y0349 only Resistor Kit catalog number 47W97 required and ordered separately 3 Air handle...

Page 12: ...tage operation 5 Cut loop jumper clippable wire Short DS to R for Humiditrol applications This will slow the outdoor unit s fan speed to a specific RPM A wire must be installed between the DS terminal...

Page 13: ...nox units charged with HFC 410A refrigerant Residual mineral oil can act as an insulator preventing proper heat transfer It can also clog the expansion device and reduce sys tem performance and capaci...

Page 14: ...oor unit s liquid line orifice housing LOW HIGH EXISTING INDOOR UNIT GAUGE MANIFOLD CYLINDER CONTAINING CLEAN HCFC 22 TO BE USED FOR FLUSHING Positioned to deliver liquid refrigerant LIQUID LINE SERVI...

Page 15: ...itrogen flow will have an exit point NITROGEN HIGH LOW B A C PIPING PANEL REMOVAL PREPARING LINE SET CAP AND CORE REMOVAL Remove piping panel to access service valves Cut ends of the refrigerant lines...

Page 16: ...ater saturated cloths under the valve body to protect the base paint 4FLOW NITROGEN Flow regulated nitrogen at 1 to 2 psig through the refrigeration gauge set into the valve stem port connection on th...

Page 17: ...KIT MATCH UPS AND APPLICATION INFORMATION A REMOVE THE FIELD PROVIDED FITTING THAT TEMPORARILY RECON NECTED THE LIQUID LINE TO THE INDOOR UNIT S DISTRIBUTOR AS SEMBLY B INSTALL ONE OF THE PROVIDED TEF...

Page 18: ...der of HFC 410A refrigerant to the center port of the manifold gauge set Open the valve on the HFC 410A cylinder vapor only B Open the high pressure side of the manifold to allow HFC 410A into the lin...

Page 19: ...ge caused by deep vacuum operation will void warranty OUTDOOR UNIT TO VAPOR SERVICE VALVE TO LIQUID LINE SERVICE VALVE MICRON GAUGE VACUUM PUMP A34000 1 4 SAE TEE WITH SWIVEL COUPLER 500 MANIFOLD GAUG...

Page 20: ...30 minutes minimum at the deep vacuum level Deep Vacuum Gauge Response and System Conditions FIGURE 19 Triple Evacuation Method The triple evacuation method should only be used when system does not c...

Page 21: ...ting to the outside coil tub ing The location of the coil sensor is important for proper defrost operation NOTE The heat pump control accurately measures the performance of the system as frost accumul...

Page 22: ...els must be in place any time the unit is in operation If you are unsure about the filter required for your system call your Lennox dealer for assistance IMPORTANT Sprinklers and soaker hoses should n...

Page 23: ...unit 3 Check the cleanliness of indoor blower and clean blower if necessary 4 Inspect the indoor coil drain pans and condensate drains for rust debris obstructions leaks or cracks Pour water in pans...

Page 24: ...ies with Y2 out terminal on the outdoor control 5 Cycle main power ON 6 Allow pressures and temperatures to stabilize before taking any reading may take up to 10 minutes 7 Record all of the readings f...

Page 25: ...st Stage Expected results during Y2 demand toggle switch ON Y2 Second Stage Compressor Voltage Same Same Amperage Higher Higher Condenser Fan motor Amperage Same or Higher Same or Higher Temperature A...

Page 26: ...ure Return Air Temperature HEATING MODE Vapor Pressure Liquid Pressure Supply Air Temperature Ambient Temperature Return Air Temperature System Refrigerant Charge Refer to manufacturer s information o...