background image

13

Wiring Connections

WARNING

!

Isolate the power supply before accessing unit 

electrical terminals.

Install unit so that unit disconnect is accessible.

Follow all local and national codes, as well as this 

installation instruction, during installation. Do NOT 

overload electrical circuit, as this may lead to failure 

and possible fire.

Use  specified  wiring  and  cable  to  make  electrical 

connections. Clamp cables securely and make sure 

that connections are tight to avoid strain on wiring. 

Insecure wiring connections may result in equipment 

failure and risk of fire. 

Wiring must be installed so that all cover plates can 

be securely closed.

In the U.S.A., wiring must conform with current local codes 

and the current National Electric Code (NEC). In Canada, 

wiring must conform with current local codes and the current 

Canadian Electrical Code (CEC). Refer to unit nameplate 

for minimum circuit ampacity and maximum overcurrent 

protection size.

NOTE - Three-conductor shielded cable must be used for 

the communication wiring. This is necessary to ensure 

proper system communication and operation.

CAUTION

!

This unit must be properly grounded and protected 

by a circuit breaker. The ground wire for the unit must 

not be connected to a gas or water pipe, a lightning 

conductor or a telephone ground wire. 

Do not connect power wires to the outdoor unit until 

all other wiring and piping connections have been 

completed.

Install all wiring at least 3 feet away from televisions,  

radios or other electronic devices in order to avoid 

the possibility of interference with the unit operation. 

Do not install the unit near a lighting appliance that 

includes  a  ballast.  The  ballast  may  affect  remote 

control operation.

Tightening torque for the terminal screws

• 

Use  the  correct  screwdriver  for  fighting  the  terminal 

screws. If the screwdriver blade is too small, the head 

of the screw might be damaged, and the screw will not 

be properly tightened.

•  If the terminal screws are over tightened, screws might 

be damaged.

•  Refer to the table below for the tightening torque of the 

terminal screws.

A disconnection device having an air gap contact 

separation in all active conductors should be 

incorporated  in  the  fixed  wiring  according  to  the 

National Wiring Regulation.

CAUTION

!

Table 3. Terminal Screw Tightening Torque

Tightening torque (lb-ft)

Terminal base of 

remote controller/Signal 

transmission wire (X2M)

0.58-0.72

Terminal base of power 

supply (X1M)

0.87-1.06

Grounding terminal (M4) 1.06-1.43

• 

After wiring, confirm all connections are correct; Then 

turn on power supply to the unit.

1. 

Pull  the  return  air  filter  grille  forward  and  remove  the 

filters.

2.  Remove one screw from each safety strap assembly 

(one on each side) and remove return air grille.

3.  Locate the control box in the center of the unit, below 

and behind the fan motor.

4.  Remove the two screws holding the control box onto the 

motor mounting bracket, and the screw at each end of 

the control box holding securing the box to the chassis 

of the unit. Lower the control box to obtain access to 

cover.

5.  Remove the screws securing the cover and remove 

cover from control box.

6.  Locate the terminal strip in the control box. Connect the 

power wiring (sized per NEC/CEC  and  local codes) 

and communications cable (three-conductor shielded 

cable) per figures 12 and 13. Refer to unit nameplate 

for rated voltage.

7. 

If the indoor unit is the final unit in a group that is wired 

in series, install the provided resistor across terminals P 

and Q. See figure 14.

•  A circuit breaker capable of shutting down the power 

supply to the entire system must be installed.

•  A single switch can be used to supply power to units on 

the same system. However, branch switches and circuit 

breakers must be selected carefully.

•  Fit the power supply wiring of each unit with a switch 

and fuse as shown in the wiring diagram.

•  Install a wiring interrupter or ground-fault circuit 

interrupter for the power wiring.

•  Make sure the ground resistance is no greater than 

100Ω. This value can be as high as 500Ω when using 

a grounding fault circuit interrupter since the protective 

ground resistance can be applied.

Summary of Contents for VSCA Series

Page 1: ...Consult authorities having jurisdiction before installation WARNING Improper installation adjustment alteration ser vice or maintenance can cause property damage personal injury or loss of life Instal...

Page 2: ...uh 018 18 000 Btuh 024 24 000 Btuh Voltage P 208 230V 1 phase 60hz System Piping CAUTION VRF system piping is customized for each installation The LVSS piping report is an engineered design that must...

Page 3: ...2 495 19 1 2 495 23 1 4 591 23 1 4 591 C 30 762 38 3 4 984 43 1 2 1105 43 1 2 1105 D 14 3 4 375 14 3 4 375 15 3 8 391 15 3 8 391 RIGHT SIDE VIEW LIQUID PIPE GAS PIPE C TOP OF UNIT AIR FLOW BOTTOM OF U...

Page 4: ...feet accessory Model Cat LIQUID PIPE GAS PIPE AIR FLOW AIR FLOW RETURN AIR OPENING ELECTRICAL CONTROL BOX CONDENSATE DRAIN CONNECTION CONDENSATE DRAIN CONNECTION ELECTRICAL CONTROL BOX FILTER ACCESS...

Page 5: ...3 8 391 15 3 8 391 G 36 914 44 5 8 1133 49 3 8 1254 49 3 8 1254 H 18 1 2 470 18 1 2 470 22 1 4 565 22 1 4 565 RIGHT SIDE VIEW LIQUID PIPE GAS PIPE SUPPLY AIR OPENING TOP OF UNIT AIR FLOW BOTTOM OF UN...

Page 6: ...GAS PIPE AIR FLOW RETURN AIR OPENING ELECTRICAL CONTROL BOX AIR FLOW ELECTRICAL CONTROL BOX CONDENSATE DRAIN CONNECTION CONDENSATE DRAIN CONNECTION CONDENSATE DRAIN CONNECTION FILTER ACCESS Dimensions...

Page 7: ...3 1 2 89 TOP 59 1499 SIDE 6 152 Optional Feet Accessory V8VSA001 3P 19X68 BACK 2 51 BOTTOM 3 1 2 89 SIDE 24 610 SIDE 6 152 TOP 59 1499 VSCA Floor Standing Cased Mounted on Wall VSCA Floor Standing Cas...

Page 8: ...Mounted on Wall VSEA Floor Standing Exposed with Optional Feet Accessory BOTTOM 3 1 2 89 SIDE 24 610 SIDE 6 152 TOP 59 1499 Base Optional Feet Accessory V8VSA001 3P 19X68 BACK 2 51 SIDE 24 610 SIDE 6...

Page 9: ...oled Ensure the structural wall or floor can support the weight of the unit Select a location where condensate line will have the shortest run to a suitable drain per local codes Installation 1 Locate...

Page 10: ...rmally high operating pressures and may result in system failure or explosion Insulate all refrigerant piping Refrigerant pipes may be very hot during unit operation Do not allow contact between wirin...

Page 11: ...t connections and field supplied insulated piping All field piping connections shall be insulated and air tight to prevent unwanted condensation build up Figure 6 Flared connections should always be a...

Page 12: ...re that the line will drain freely 5 After the system installation is complete the condensate drain line must be checked for leaks and proper drainage If a field provided condensate pump has been inst...

Page 13: ...over tightened screws might be damaged Refer to the table below for the tightening torque of the terminal screws A disconnection device having an air gap contact separation in all active conductors s...

Page 14: ...230V 3Ph 60Hz or 460V 3Ph 60Hz Power supply 208 230V 1Ph 60Hz Power supply Mode Selection Box Indoor unit Indoor unit Indoor unit Dedicated breaker Service Disconnect L1 L2 L1 L2 Fuse Service Disconn...

Page 15: ...polarity sensitive Typical Wiring Diagram NEC CEC and Local Codes apply Outdoor unit Outdoor unit sub1 unit Outdoor unit sub2 unit PQ main unit PQ MS Box PQ PQ MS Box PQ PQ H1 H2 H1 H2 H1 H2 Outdoor...

Page 16: ...nd Q of the daisy chain P Q All shields of shielded cable connect to chassis GROUND terminal at Indoor Units 18 GA stranded 2 conductor shielded control wire polarity sensitive Typical Wiring Diagram...

Page 17: ...r CN14 GM1 GM2 XP6 XP4 XP3 XP2 XP1 BLUE BLACK WHITE RED XS4 XS3 XS2 XS1 XS6 XP7 XS7 CN12 NOTE 1 Refer to manual for communication wiring 2 Please use the 2 conductor shielded twisted cable for communi...

Page 18: ...nd and tools to metal prior to handling the control IMPORTANT V0STAT55P 3 is an optional wired non programmable lo cal controller that controls VSC VSE Floor Standing indoor units These instructions a...

Page 19: ...trol Board Back of Controller 10 Conductor Wiring Harness Display Receiver Panel 5 Conductor Wiring Harness To Indoor Unit Main Board Connect to Receiver Connect to Controller Wiring Harness Plug into...

Page 20: ...down arrow buttons to adjust the set point When in Auto mode separate heating and cooling setpoints can be set Press the Mode button to switch between heat ing and cooling setpoints Backlight The back...

Page 21: ...information can also be obtained using the wired remote controller No Content Recorded Value Date 0 Normal display 1 Communication address of indoor unit 2 Indoor unit capacity horsepower 3 Network ad...

Page 22: ...roken and restored at the disconnect switch or circuit breaker call VRF Technical Support 1 844 438 8731 Troubleshooting Figure 19 Receiver Display Error Code Description FE No address E0 Mode conflic...

Page 23: ...23 Technical Support 1 844 GET VRF1 1 844 438 8731 vrftechsupport lennoxind com www LennoxVRF com Download the app from the Apple App Store or the Google Play store...

Reviews: